Back-UPS® Pro Installation and Operation
3
Operation
Power-Saving Function
To conserve electricity, configure the Back-UPS to recognize a Master device, such as a desktop 
computer or an A/V receiver, and Controlled peripheral devices, such as a printer, speakers, or a scanner. 
When the Master device goes into Sleep or Standby mode, or is switched OFF, the Controlled device(s) 
will be switched off as well, saving electricity.
Enable the Power-Saving function. 
Press and hold 
M
UTE
 and 
D
ISPLAY
 simultaneously for two seconds. The 
Back-UPS will beep to indicate that the feature is enabled. The leaf icon on the display will illuminate.
Disable the Power-Saving function. 
Press and hold 
M
UTE
 and 
D
ISPLAY
 simultaneously for two seconds. The 
Back-UPS will beep to indicate that the feature is disabled. The leaf icon on the display will darken.
Setting the threshold. 
The amount of power used by a device in Sleep or Standby mode varies between devices. It 
may be necessary to adjust the threshold at which the Master outlet signals the Controlled outlets to shut down.
1. Ensure a master device is connected to the Master outlet. Put that device into Sleep or Standby mode, or turn it 
OFF.
2. Press 
D
ISPLAY
 and 
M
UTE
 simultaneously and hold for six seconds, until the leaf icon flashes three times and the 
Back-UPS beeps three times.
3. The Back-UPS will now recognize the threshold level of the Master device and save it as the new threshold setting.
Power-Saving Display 
The display interface can be configured to be continuously illuminated, or to save energy, it can be configured to 
darken after a period of inactivity.
1. Full Time Mode: Press and hold 
DISPLAY
 for two seconds. The display will illuminate and the Back-UPS will beep 
to confirm the Full-Time mode. 
2. Power-Saving Mode: Press and hold 
DISPLAY
 for two seconds. The display will darken and the Back-UPS will 
beep to confirm the Power-Saving mode. While in Power-Saving Mode, the display will illuminate if a button is 
pressed, it then darkens after 60 seconds of no activity. 
Unit sensitivity 
Adjust the sensitivity of the Back-UPS to control when it will switch to battery power; the higher the sensitivity, the 
more often the Back-UPS will switch to battery power. 
1. Ensure the Back-UPS is connected to utility power, but is OFF.
2. Press and hold the
 P
OWER
 button for six seconds. The 
L
OAD
 C
APACITY
 bar will flash on and off, indicating that the 
Back-UPS is in programming mode.
3. Press
 P
OWER
 again to rotate through the menu options. Stop at selected sensitivity. The Back-UPS will beep to 
confirm the selection.
Generator Sensitivity
Default
Sensitive Loads
Low sensitivity
Medium sensitivity (Default)
High sensitivity
78-142 Vac
88-139 Vac
88-136 Vac
Input voltage is extremely low or 
high. (Not recommended for 
computer loads.)
The Back-UPS frequently switches to 
battery power.
The connected equipment is 
sensitive to voltage fluctuations.