Troubleshooting: UPS Alarms
22
Symmetra PX 160 kW 400 V Operation
990-3015-001
External DC Disconnect Switch 
Open
The external
 DC 
DISCONNECT
 switch 
tripped. Battery power is not 
available or the runtime is lower than 
expected.
Close the external 
DC D
ISCONNECT
 switch. 
Check the fuse on the XR battery 
enclosure. If the fuse has blown, contact 
APC Customer Support.
External Switch Gear 
Communication Card Fault
The external switch gear 
communication card has failed.
External Switch Gear 
Communication Card Removed
The system no longer detects an 
external switch gear communication 
card.
Option 1: Ensure the external switch gear 
communication card is installed properly.
Option 2: Replace the external switch gear 
communication card.
Graceful Shutdown Initiated
A graceful shutdown or reboot has 
been initiated from the display 
interface or other accessory.
No corrective action necessary.
High Isolation Transformer 
Temperature
The isolation transformer 
temperature is too high.
Contact APC Customer Support.
Internal Communications Failed One of the buses used for the 
communication between the UPS 
modules has failed.
Contact APC Customer Support.
In Bypass: Hardware Fault
The system has transferred into 
bypass because a fault has occurred.
Contact APC Customer Support.
In Bypass: Overload
The system has transferred into 
bypass because the load has 
exceeded the power capacity of the 
system.
Option 1: Decrease the load.
Option 2: Add a power module to the 
system.
In Bypass: User-Initiated
The system has been transferred into 
bypass due to user action.
Check for any problems with the system. 
Transfer the system to normal operation.
Input Voltage or Frequency 
Cannot Support Bypass
The frequency or voltage is out of 
acceptable range for bypass. This 
message occurs when the UPS is 
online, and indicates that the bypass 
mode may not be available if 
required.
Correct the input voltage to provide 
acceptable voltage or frequency.
Intelligence Module Fault
The main intelligence module has 
failed and requires replacement.
Load (kVA) Alarm Violation
The load has exceeded the user-
specified load alarm threshold.
Option 1: Use the display interface to raise 
the alarm threshold.
Option 2: Reduce the load.
Local Management-To-UPS 
Communication Lost
Internal communications in the 
system have failed.
Contact APC Customer Support.
Display Message
Meaning
Corrective Action