APC 10-40 KVA 380/400/415 V User Manual
Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation
8
Anchor the UPS and additional XR Battery or UPS
Enclosure(s) (optional)
Note: Enclosures can be kept apart or assembled and anchored with interconnection plates and
brackets: SUVTOPT004: 352 mm (13.85 in) UPS enclosure to XR enclosure, SUVTOPT005:
523 mm (20.59 in) UPS enclosure to XR enclosure, or SUVTOPT006: XR enclosure to XR
enclosure.
brackets: SUVTOPT004: 352 mm (13.85 in) UPS enclosure to XR enclosure, SUVTOPT005:
523 mm (20.59 in) UPS enclosure to XR enclosure, or SUVTOPT006: XR enclosure to XR
enclosure.
Note: A baying kit includes three U-shaped floor anchoring brackets. In situations where a
UPS or XR Battery Enclosure must be added to an existing configuration of two or more bayed
together enclosures, only one of the U-shaped floor anchoring brackets is necessary. In those
situations, please dispose of the two superfluous U-shaped floor anchoring brackets.
UPS or XR Battery Enclosure must be added to an existing configuration of two or more bayed
together enclosures, only one of the U-shaped floor anchoring brackets is necessary. In those
situations, please dispose of the two superfluous U-shaped floor anchoring brackets.
Note: The L-shaped floor anchoring brackets that secured the enclosure to the pallet during
shipment may be used for a stand-alone UPS enclosure to enhance stability, but is not
necessary when baying enclosures together. Instead, the three U-shaped floor anchoring
brackets from the baying kit are used.
shipment may be used for a stand-alone UPS enclosure to enhance stability, but is not
necessary when baying enclosures together. Instead, the three U-shaped floor anchoring
brackets from the baying kit are used.
1. Remove the side panels from the
enclosure(s) to get access to the holes in
the bottom frame.
the bottom frame.
Note: Make sure that the enclosures
are level to be able to anchor the enclosures to each other.
are level to be able to anchor the enclosures to each other.
2. Position two U-
shaped floor
anchoring
brackets under
one enclosure;
one in each
side.
anchoring
brackets under
one enclosure;
one in each
side.
UPS
XR
Front of enclosure
Front of adjacent
enclosure
enclosure
U-shaped floor
anchoring
bracket