APC 10-40 KVA 380/400/415 V User Manual

Page of 32
23
Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation
Specifications 
Battery voltage and current 
Recommended cable sizes
Note: Power terminal lug diameter: minimum 6 mm (0.2 in). 
Torque value: 45 lbf-in/7 Nm.
Note: Use Molex lug type or equivalent, and follow the manufacturer’s specifications.
EPO requirements
Torque specification
Torque specification: Isolators: M5 7 Nm (45 lbf-in).
XR Battery Enclosure
30 kVA
40 kVA
Battery voltage (nominal)
± 192 VDC
± 192 VDC
Battery current (at full load)
69.4 A at ± 192 V
87.9A at ± 192V
Max. current (at end of discharge)
86.6 A at ± 154 V
110.1A at ± 154V
If the XR Battery Enclosure is customer-supplied, please refer 
to product-specific data.
North America
Europe, Middle East, Asia
Japan
208/220 V
380/400/415 V 
200/208 V
BAT+, N, BAT- 1 AWG 167º F 
(75º C) copper wire
BAT+, N, BAT- 50 mm
2
 75º C 
(167º F) copper wire
BAT+, N, BAT- 50 mm
2
 75º C copper 
wire.
Use only 8,08-1,3 mm
copper wire rated 
minimum 250 V.
SELV voltage
24 VDC
Current:
1500 mA