APC 100-127 V User Manual

Page of 20
Smart-UPS X 2000/2200/3000 VA  
8
Configuration
UPS Settings
Start-up Settings
Use the display interface to configure these settings at initial start-up. The UPS will prompt for a 
response to each setting, if no response is given, the default setting will be used. 
Note: The unit will not turn on until all of these settings are entered.
Function
Factory Default
Options
Description
Language
English
• English
• French*
• German*
• Spanish*
• Italian*
• Portuguese*
The language for the display interface.
*Language options will vary by model.
Output 
Voltage
Low Voltage: 120 V • 100
• 110
• 120
• 127
Set the output voltage setting while the UPS is in 
Standby mode. 
High Voltage: 230 V • 200
• 208
• 220
• 230
• 240
Input Power 
Quality
Good
• Good
• Fair
• Poor
Select the quality of input utility power.
• If Good is selected, the unit will go on battery 
power more often to provide the cleanest power 
supply to the connected equipment.
• If Poor is selected, the UPS will tolerate more 
fluctuations in power and will go on battery power 
less often. 
If unsure of the local power quality, select Good.
Menu Type
Standard
Standard or 
Advanced
The advanced menus include all parameters. The 
Standard menus display a limited set of menus and 
options.
Date
UPS manufacture 
date + 90 days
mm-yyyy
Enter the current date.