Rectifier Terminal 
Function
Terminal 
# Function Terminal 
Function 
Rectifier 1 
TRM2 
Ground 
TRM5 
Line or Neutral 
TRM8 
Line 
Rectifier 2 & 3 
TRM3 
Ground 
TRM6 
Line or Neutral 
TRM9 
Line 
Rectifier 4 & 5 
TRM4 
Ground 
TRM7 
Line or Neutral 
TRM10 
Line 
Chassis TRM1 
Ground   
 
 
 
Figure 3.3-3 AC Input Wiring 
 
AC Power Cord Sets 
 
AC input cable kits are available from APC.  These cables are 12 feet (3.7m) long and have a 
power plug installed on each cable.  When ordered with the power system, these cables will be 
installed with strain reliefs provided to mount the 3-conductor jacketed cables.  Each kit will 
supply power to the entire power system.  Use the chart in Figure 3.3-5 to determine the 
suggested cable kits.   
 
Part Num. 
AWG 
Cable Qty  Plug Num. 
Plug Style 
Voltage  Power System 
0M-91157 
14 
NEMA 5-15 
Non-locking 
115 
Magnum VS 50 
0M-91155 
14 
NEMA L5-15 
Locking 
115 
Magnum VS 50 
0M-91156 
12 
NEMA 5-20P 
Non-locking 
115 
Magnum VS 50 
0M-91154 
12 
NEMA L5-20P  Locking 
115 
Magnum VS 50 
0M-91158 
10 
NEMA 5-50P 
Non-locking 
115 
Magnum VS 50 
0M-1150 
12 
NEMA L6-20P  Locking 
230 
Magnum VS 50 
0M-91160 
10 
NEMA 6-30P 
Non-locking 
230 
Magnum VS 50 
0M-91159 
10 
NEMA L6-30P  Locking 
230 
Magnum VS 50 
0M-91137 
12 
NEMA 5-15P 
Non-Locking 
115 
Magnum VS 100 
0M-91140 
12 
NEMA L5-15P  Locking 
115 
Magnum VS 100 
0M-91138 
12 
NEMA 5-20P 
Non-locking 
115 
Magnum VS 100 
0M-91141 
12 
NEMA L5-20P  Locking 
115 
Magnum VS 100 
0M-91139 
10 
NEMA 5-50P 
Non-locking 
115 
Magnum VS 100 
0M-1149 
12 
NEMA L6-20P  Locking 
230 
Magnum VS 100 
0M-91135 
10 
NEMA 6-30P 
Non-locking 
230 
Magnum VS 100 
0M-91136 
10 
NEMA L6-30P  Locking 
230 
Magnum VS 100 
Figure 3.3-5 Power Cord Sets 
 
 
WARNING:  Hazardous ac voltage levels are present inside the power 
system.  Keep the rear cover in place when the system is operational or 
energized.  
 
The rear cover of each shelf in the power system is provided with two 1.125-inch (2.858 cm) 
diameter holes for electrical conduit.  Conduit can be run to each shelf or strain reliefs are 
provided to install jacketed cables.