APC VS 100 User Manual

Page of 65
Magnum VS –48 Vdc User’s Manual 
                                     
  Page 19 
Output Relay 1: 
 
1.  Minor and Major output relays were tested in the rectifier test section. 
2.  Change the alarm to desired relay output via the controller for any relay output that will be 
used.  All alarm parameters are shipped as either major or minor, but may be changed to 
output relay 1.   
3.  Program output relay 1 to desired major or minor alarm to complete programming. 
4.  Exercise the output relay by causing the alarm to change state. 
 
Battery Temperature Compensation 
 
1.  Enable battery temperature compensation if desired. 
2.  Ensure that battery temperature probe is connected to the system and attached to the 
battery. 
3.  Verify that the system voltage is above the float voltage setting if the battery temperature 
is below 25 degrees C and below the float voltage setting if the battery temperature is 
above 25 degrees C. 
 
4.3. Final Inspection: 
 
1.  Verify that the interior and exterior of the system is clean and free from debris. 
2.  Ensure all wires connected and bolts are properly tightened. 
3.  Ensure the following the User, Service, and Calibration parameters are set properly on 
the controller: 
LVD 
 LVD1 
Trip 
 
 LVD1 
Reset 
Battery Parameters  
 Discharge 
Threshold 
 Float 
Voltage 
 Maximum 
Recharge 
 Compensation 
Method 
4.  Verify that the system is functioning correctly with no alarms. 
Be sure to leave the site as orderly and neat as possible.