Magnum VS –48 Vdc User’s Manual 
                                     
  Page 21 
System Current Monitor 
 
The controller monitors individual rectifier currents and displays total system current as a sum of 
rectifier currents.  Load current can be found by adding battery current to system current.  
Battery Current is positive when the battery is discharging.   
 
Sys Current + Batt current = Load Current 
 
For example, if the battery is charging the Batt Current reading could be (–) 10 A, Sys Current 
reading could be 50 A.  Load Current would be: 
 
Sys Current + Batt current = Load Current 
50 A + (-) 10 A = 40 A.   
 
If the battery is discharging the Batt Current reading could be 10 A, Sys Current reading could 
be 30 A.  Load current would be: 
 
Sys Current + Batt current = Load Current 
 30 A + 10 A = 40 A.
  
 
System Status and Alarm Reporting 
 
The controller will monitor system, temperature.  The controller reports system high and low 
temperature alarms. 
 
5.3. Load Management 
 
Circuit Breakers 
 
Distribution is included for up to 2 circuit breakers or eight GMT fuses per 50-A shelf.  The circuit 
breakers can be 2 X 30 A or 1 X 60 A in each shelf.  The GMT fuses are 8 X ¼ to 15 A in each 
shelf.   When a circuit breaker trips, a normally open switch closes and the controller reports a 
CB alarm.  Alarms are reported only when a breaker is tripped.  When a breaker is turned off, no 
alarm is generated.  Circuit Breaker Alm 1 or 2 are reported when a circuit breaker in the top 
shelf trips.  Circuit Breaker Alm 3 or 4 are reported when a circuit breaker in the bottom shelf 
trips.  Because of this, if a Magnum VS 100 has GMT fuses in the top shelf and 2 circuit 
breakers in the bottom shelf, the circuit breakers will be labeled CB1 & CB2 on the front panel, 
but Circuit Breaker Alarm 3 & 4 will be reported.  If a Magnum VS 100 has GMT fuses in the top 
shelf and 1 circuit breaker in the bottom shelf, the circuit breaker will be labeled CB1 on the front 
panel, Circuit Breaker Alarm 3 will be reported.  If a Magnum VS 100 has 1 circuit breaker in the 
top shelf and 1 circuit breaker in the bottom shelf, the circuit breakers in the bottom shelf will be 
labeled CB2 on the front panel, but Circuit Breaker Alarm 3 will be reported.  To disconnect a 
load attached to a circuit breaker, move the lever down to the “OFF” position.