Page 54
Magnum VS 100 Power System
Input Voltage Range
Input Voltage Range
85 – 264 Vac
AC Frequency Range
47 – 63 Hz
Apparent Power Factor
99% Typical, 98% Minimum
Input Current
55 A @ 115 Vac
37 A @ 230 Vac
37 A @ 230 Vac
9.2. DC Output
TWF0500H54B Rectifier
Output Voltage (factory set) 54.5 Vdc
Operating Voltage Range
44 – 58 Vdc
Efficiency 85%
Typical
Over Voltage Protection
59.5 Vdc
Output Current per
Rectifier
Rectifier
9.0 A Minimum Continuous at 115 Vac Input
10.5 A Minimum Continuous at 230 Vac Input.
10.5 A Minimum Continuous at 230 Vac Input.
Current Limit
9.3 A Maximum at 115 Vac Input
11.0 A Maximum at 230 Vac Input.
11.0 A Maximum at 230 Vac Input.
Power Output per Rectifier
@ 54.5Vdc
@ 54.5Vdc
490 W Continuous at 115 Vac Input
570 W Continuous at 230 Vac Input
570 W Continuous at 230 Vac Input