APC SY160K160H User Manual

Page of 36
990-3015-001
Symmetra PX 160 kW 400 V Operation 
7
Operation
Operation Modes
In an installation without a maintenance bypass panel, the UPS has four different operation modes. If 
the installation includes a PDU-XR or an external maintenance bypass panel, wrap-around 
maintenance bypass mode will also be available.
Normal operation
During normal operation, the UPS converts mains/utility power to conditioned power for the 
connected loads. 
Battery operation
During battery operation, the UPS provides power to the connected loads from its external batteries 
for a finite period. The UPS transfers to battery operation if the supply of mains/utility power fails, or 
is outside pre-defined limits. 
Bypass operation 
Bypass is a feature that keeps the load supplied with mains/utility power during maintenance of the 
UPS power sections. In bypass, mains/utility power is sent directly to the connected load bypassing 
all internal UPS functions and filters. Battery back up is not available in bypass operation.
Wrap-around maintenance bypass (optional)
The UPS can be connected to a PDU-XR or an optional external maintenance bypass panel. When 
activated, this panel bypasses the UPS, feeding mains/utility power directly to the load. An activated 
wrap-around maintenance bypass panel completely isolates the UPS and allows maintenance to be 
performed - including a replacement of the entire UPS.