Symmetra PX 160 kW 400 V Operation
21
Troubleshooting
UPS Alarms
This section lists all of the alarm and status messages that might be displayed on the display interface. 
A suggested corrective action is listed with each message to help to troubleshoot the problem.
Note: If a problem is reported, ensure that the system component in question is correctly 
installed.
1
Display Message
Meaning
Corrective Action
Battery Charger Fault
The battery charger is not 
functioning properly.
Contact APC Customer Support.
Battery Fault
A battery module has failed and 
requires replacement.
Battery High Temperature 
Violation
The temperature of one or more 
battery units has exceeded system 
specifications.
Ensure that the ambient temperature meets 
the specifications of the system. If the 
ambient temperature is below 40°C 
(104°F). Initiate a self-test to detect any 
bad battery units. Replace any bad battery 
units.
Battery High Voltage Violation
The battery voltage is too high and 
the charger has been deactivated.
Contact APC Customer Support.
Battery Monitor Card Fault
The battery monitor card has failed.
Battery Monitor Card Removed The battery monitor card has been 
removed.
If the battery monitor card has not been 
removed, check that is has been properly 
inserted.
Bypass Relay Stuck in Bypass 
Mode
The system is stuck in bypass mode 
and cannot return to normal 
operation.
Check the static bypass switch. Contact 
APC Customer Support.
Bypass Relay Stuck in Online 
Mode
The system is stuck in online mode 
and cannot go into bypass.
Check the static bypass switch. Contact 
APC Customer Support.
Communication Lost While On 
Battery
Internal communications in the 
system have failed.
Contact APC Customer Support.
Discharged Battery
The UPS is online and the battery 
charge is low.
No corrective action necessary. Note: If the 
input voltage fails, runtime will be limited.
Extended Run Frame Fault
One of the battery frames has failed. Contact APC Customer Support.