APC METERED RACK-MOUNT PDU AP7621 User Manual

Product codes
AP7621
Page of 32
PDU: User’s Manual
1
Product Descriptions and Safety Information
Features of 
single-branch 
PDU models
This manual explains how to install and use the following 
Rack-mount PDUs:
All the PDUs distribute input power from a single source to the 
PDU outlets for use by connected equipment and provide 
current-sensing to guard against overload conditions.
Safety 
information
PDU
Voltage
Number of 
Outlets
Outlet Type
AP7620
 
100
120
 
VAC
24
 
NEMA
 
5
-
20R
 
AP7622
 
200
240
 
VAC
6
 
NEMA
 
L6
-
20R
 
AP7621
 
AP7626
 
200
240
 
VAC
25
 
21 outlets of type 
IEC 320
 
C13
4
 outlets of type 
IEC 320
 
C19
Note
In all applications, the plug on the power supply 
cord is the means to disconnect the 
PDU
. The 
receptacle (outlet) into which the 
PDU
 is plugged 
must be installed near the connected equipment 
and must be easily accessible.
In 
208
 and 
230
 
VAC
 applications, the 
PDU
 relies 
on the building installation for over-current and 
short-circuit current protection.
You must connect the 
PDU
 to a branch circuit 
that is rated as follows:
20
 amps, 
250
 volts (in accordance with 
NFPA
 
70
) in 
208
 
VAC
 applications.
16
 amps, 
250
 volts in 
230
 
VAC
 
applications.