APC 19inch x 3u x 12inch SHELF (3xMRF14) 1MS14A User Manual
![APC](https://files.manualsbrain.com/attachments/434134065d5c651f4d733496e262a45a75ce3ca6/common/fit/150/50/cb1a8b6f231ef4d783dd99279a1457344a0d4d6facb230ab9b5ba2f65edf/brand_logo.png)
Product codes
1MS14A
PowerDeck shelves: Instructions
®
990-9070 Rev 1
Page 8 of 8
May 2001
5. Settings and adjustments
5.1 Jumper Links
The node card has two jumper links fitted, J1 and J2, these are illustrated in figure 4.1 below which shows a
section of the node card. The configuration of these should be set when the shelf is installed using the
information table 5.1 below.
Jumper
Controls
Operation when fitted
Operation when NOT fitted
J1
Post mate enable
Rectifiers run with no additional connections
PL5 pin 19 must be connected to PL5 pin 15
for the rectifiers to run. Can be used as
remote inhibit function.
for the rectifiers to run. Can be used as
remote inhibit function.
J2 Signal
ground
Signals common (PL6 pin 6, PL5 pin 10) is
connected to negative sense (PL6 pin 12,
PL5 pin 15).
connected to negative sense (PL6 pin 12,
PL5 pin 15).
Signals common isolated from negative
sense.
sense.
Table 5.1
5.2 Output voltage setting
Potentiometer P1 on the node card adjusts the output voltage of all the rectifiers simultaneously, its position is
illustrated in figure 5.1 below. It is also adjustable through a hole in the shelf rear panel. The Vtrim signal being
fed to the rectifiers can be measured on TP1 (TP2 is 0V). An input of 5.0V results in no adjustment of the rectifier
voltages.
illustrated in figure 5.1 below. It is also adjustable through a hole in the shelf rear panel. The Vtrim signal being
fed to the rectifiers can be measured on TP1 (TP2 is 0V). An input of 5.0V results in no adjustment of the rectifier
voltages.
Figure 5.1
J1,J2
P1
TP2 TP1
PL5
PL6