3.7.
Connecting the control signals
For all applications with conventional controllers ( such as NT6C25BA or
NT6C25BB ) or front access controllers ( NT6C25FA ), execute the steps
contained in Procedure 7 to connect the NT5C05CC rectifier ( see Figure
9 ).
NT6C25BB ) or front access controllers ( NT6C25FA ), execute the steps
contained in Procedure 7 to connect the NT5C05CC rectifier ( see Figure
9 ).
Procedure 7 - Connecting the NT5C05CC to the controller
Step Action
1
Connect each rectifier to the NT6C43PB board ( positions J1 to J6 ),
located at the top front of the cabinet or frame, with P0747000
cables.
located at the top front of the cabinet or frame, with P0747000
cables.
2
•
Connect the NT6C43PB board ( positions J7 to J12 ) to the
controller with P0736355 cables for conventional controllers ;
and with P0736268 cables for front access controllers.
and with P0736268 cables for front access controllers.
end
Figure 9 - Typical connections between rectifiers and the conventional
controller
Rectifier
# 6
J13
J1
J2
J3
J4
J5
J6
J7
J8
J9
J10
J11
J12
MONITOR
NT6C43PB
Cables P0736355
CONTROLLER NT
(NT6C25BA or NT6C25BB)
Cables P0747000
Rectifier
# 5
Rectifier
# 4
Rectifier
# 3
Rectifier
# 2
Rectifier
# 1