Emerson 200I/48-NT5C05C User Manual

Page of 62
34   Functional description 
UM5C05C   P0745680   Standard 6.00   October 2001 
Emerson Energy Systems 
4.2.3.  Front panel LEDs  
Table 10 - Designation of the LEDs on the front panel 
LED Color 
Description 
AC ON 
Green 
Input ac voltage operational 
CL Yellow 
Current 
Limit 
EQL 
Yellow 
Rectifier is in equalize mode 
FAN ALM 
Red 
Fan fail alarm 
HVSD 
Red 
High voltage shutdown 
RFA 
Red 
Rectifier fail alarm 
SEN FAIL 
Red 
Remote sense fail 
THSD Red 
Thermal 
shutdown 
AC ON ( ac voltage monitoring ) 
The rectifier monitors the input voltage and if the voltage exceeds the set 
limit, it will inhibit its operation and trigger a rectifier failure alarm 
( RFA ). The rectifier will resume its normal operation automatically when 
the specified input voltage has been re-established. 
CL ( current limit indicator ) 
This LED lights up if the rectifier is in current limit. The rectifier limits 
the output current to 205 A + 5 A ( adjusted in the factory ), 50% to 105% 
of the rated output current. 
EQL ( equalize ) 
Indicates the rectifier is in equalizing mode. 
FAN ALM ( fan failure alarm ) 
This LED lights up when the FAN ALM is activated due to a defect in the 
fan system. The fan configuration includes redundancy to ensure the 
rectifier will continue working properly if one of the fans fails. If only one 
fan fails, a rectifier failure alarm RFA will not be triggered. It is, however, 
imperative to repair or change the fan unit as soon as possible to preserve 
this redundant feature.