Emerson Energy Systems 
Rectifier 200I/48
NT5C05C   Installation and User Manual 
7. Troubleshooting 
Table 16 - Diagnosing system faults 
Fault symptom 
Possible causes 
The RFA LED is lit. 
• 
No ac input or input is out of bounds ( ac ON 
LED is extinguished ). 
• 
AC Input / dc output circuit breaker is open. 
• 
The rectifier has received an HVSD signal from 
the controller, or a TR signal is present. 
• 
An internal high voltage shutdown ( HVSD ) has 
occurred. 
• 
Two cooling fans or fuses have failed. 
• 
The inrush fuse has blown. 
• 
The dc circuit breaker is open. 
• 
A thermal shutdown has occurred. 
• 
Ambient air temperature is high. 
• 
Air inlet / outlet air is blocked, or the air filter is 
clogged. 
• 
A rectifier is in 'Start Time Delay' mode and the 
RFA will cease when the required time delay has 
elapsed. 
• 
Defective rectifier.
 
The HVSD LED is lit. 
• 
The internal high voltage shutdown point is set 
to low ( below the float or equalize setting ). 
• 
The controller triggered a remote HVSD.
 
−−−−
continued
−−−−