25A Switch Mode Rectifier
NT5C06B / C   Installation and User Manual 
Appendix A: NT5C10BF-1 and NT5C10BP 
Purpose 
This appendix provides additional information about the NT5C10BF-1 
(brown) and NT5C10BP (grey). 
Application 
The NT5C10BF-1 and NT5C10BP power shelves  are used in the FTIP and 
FTOP application. This power shelf provides housing for two MPR15E 
rectifiers plus one 50 A LVD, FTIP application, or three MPR25EX 
rectifiers, FTOP application. In both applications the rectifier in the center 
will be wired for standby operation (standby means that this rectifier will be 
inhibited under normal operation and will become active when another 
rectifier in the same power shelf issues an RFA). 
FTIP application 
The MPR15E (NT5C06CB/CD) rectifier is used in this application. Two 
rectifiers maximum can be used in each system, plus one 50 A LVD. The 
main rectifier is active and carries the load, and the standby is inhibited. It 
will be activated upon removal or failure of the main rectifier (hot standby 
model). 
During transfer from a failed “MAIN” unit to a “STANDBY” unit the load 
current will be supplied by the backup batteries. The standby unit will 
provide the required current within 10 seconds. 
Table 11 - Application configuration table 
Rectifier 
Qty 
Function 
Main/Standby 
LVD Alarms 
Current 
Capacity 
1 Main/None/LVD 
Yes 
RFA/LVA/LVDA  17.5 
2 Main1/Standby/LVD 
Yes 
RFA/LVA/LVDA/NSR  17.5