Appendix B:  NT5C10CO shelf   111 
25A Switch Mode Rectifier
NT5C06B / C   Installation and User Manual
 
The above settings will provide a delay of approximately 24 hours, which is 
sufficient to charge the batteries with a reserve of 80 to 120AH and at the 
same time supply power to a 10 A load. When the load is 6 A, or less on a 
battery reserve of less than 80AH, open SW1-4 and close SW1-3 for a delay 
of 12 hours. 
Troubleshooting 
The following are recommended steps for analyzing possible malfunctions of 
a system equipped with an NT5C10CO power shelf. This is in addition to 
the information contained in the “Troubleshooting” section of User Manual 
(UM) 167-9021-107. 
Table 13 - Systems equipped with NT5C10CO power shelf fault diagnosis 
Fault symptom 
Possible causes 
Delayed Start did not 
activate (delayed start 
LED is not lit): 
• 
No ACV at the power shelf input terminals. 
• 
Main rectifier has been removed or generates an RFA. 
• 
Faulty circuit pack. 
Incorrect time delay: 
• 
Verify that the SW1 switch is properly set. 
• 
Faulty circuit pack. 
—end—