Installation and start-up procedures   47 
25A Switch Mode Rectifier
NT5C06B / C   Installation and User Manual
 
23-inch system shelf (NT5C10CO) 
Capacity: 
- 1 x MPR15  + 1 x MPR15 “Delay Start” 
AC common cable 
- 2/12 AWG armored cable. Refer to Figure 13 
(side) 
DC cables 
- 6 AWG (BAT and BAT RTN). Refer to Figure 18 
(side) and to Figure 19 (rear) 
Signals: 
- 2 cables (for remote sensing and alarm) 
Note :
 
See Appendix B for additional information.
 
Figure 13 - System shelf or embedded (left view) common bussed AC - side access 
 
FR GRD
 
L2
L1
 
CAUTION
 
ATTENTIO
 
Procedure 2 - Common bussed AC connection - side access 
Step Action 
Punch out 1.125-inch dia. knockout on left side of shelf. 
Mount conduit connector with lock nut. 
Run and connect wires as illustrated. 
Re-install the blank panel to prevent access to the connections inside. 
–end–