Emerson Static Transfer Switch User Manual

Page of 152
Operating Instructions for the Touch Screen Interface
66
10.2 Manual Transfer / Preferred Source Selection
The Source Transfer option (Source Xfers) in the touch screen menu allows you to select a preferred 
source. Transfers are only permitted when the voltage and current are within their proper operating 
range and the sources are synchronized. The Source Transfer screen indicates the synchronization 
between the two sources, while the voltage and frequency are displayed on the Mimic. See Figure 46
Transfer is inhibited if the deviation exceeds the parameter set in the Source Set Points. See User 
If your system contains the LED front panel instead of the LCD touch screen, refer to 14.2.2 - Man-
ual Transfer / Preferred Source Selection for instructions on this procedure.
Figure 46 Source transfer screen
NOTE
If one source will be de-energized for an extended period (hours or days), set the unit to bypass 
mode for the remaining source. Without using bypass, if a failure occurs in the switch 
components for remaining source, the Liebert STS2 does not have a second source to switch to 
and the load would not receive power. See Maintenance Bypass on page 67 for bypass 
instructions.