Configuration: How to Configure the System
20
Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001
Change the display settings:
– Enable APC Q breaker prefix: Use this 
checkbox to enable or disable the APC Q 
breaker prefix.
– Enable audible alarms: Use this checkbox to 
enable or disable the audible alarms.
How to configure the Battery Test Settings screen
Press the Battery Test Settings button on the 
User Configuration screen to access the Display 
Settings screen.
Change the battery test settings. From the Battery 
Test Settings screen, two different battery tests 
can be performed and the battery monitor can be 
reset.
– Battery monitor test: Setting this value to True 
results in an automatic battery monitor test 
occurring dependant in the battery test options 
configured by the service engineer. 
– Battery capacity test: Setting this value to True 
results in the batteries being discharged until a 
Battery Low Voltage Level is reached. This 
test can only be performed manually. The test is used to cycle the batteries in order to calibrate 
the backup time with the current load and battery modules installed.
– Battery monitor reset: In the event of a weak battery or another battery problem, use this button 
to reset the battery monitor.