Fujitsu V6.00 User Manual

Page of 174
ServerView Event Manager
 93
Trap overview
communication
Established
8
Communication is established 
between the agent and power 
supply.
informational 
communicationLost
1
Communication between the 
agent and power supply was 
interrupted.
major
contactFault
18
One of the contacts on the 
Measure UPS has changed 
from its default position.
major
contactFaultResolved
19
An error on one of the 
Measure UPS contacts has 
been resolved.
informational 
hardwareFailure
Bypass
20
The UPS is on bypass due to a 
hardware failure.
major
lowBattery
7
The UPS system batteries are 
low and will soon be 
exhausted. If utility power is not 
restored the UPS will put itself 
to 
sleep
 and immediately cut 
power to the load.
major
powerRestored
9
Utility power has been restored 
after the occurrence of an 
upsOnBattery
 condition.
informational 
restartAgent
29
The agent was restarted on the 
command of the manager.
informational 
returnFromBypass
23
The UPS has returned from 
bypass mode.
informational 
returnFromLowBattery
11
The UPS has returned from a 
lowBattery
 condition.
informational 
smartAvrReducing
31
The UPS has enabled 
SmartAVR voltage reduction.
minor
smartBoostOn
6
The UPS has enabled
SmartBoost
.
minor
Trap name
 ID
Meaning
Error class
Table 19: APC traps