Fujitsu TX200 S6 User Manual

Page of 126
106
Operating Manual
 TX200 
S6
CSS components
Ê
Disconnect the fan cable from the connector FAN2 (if there is a second fan 
cable, disconnect this from FAN4) on the system board (see the technical 
manual for the system board D2799).
Ê
Press the two green locks of the air duct together (1).
Ê
Press the green lock of the air duct in the direction of the arrow (2).
Ê
Lift the air duct with the integrated system fan 2 (and 4) up and out (3).
8.2.1.3
Removing system fan 1 (and 3)
Ê
Remove system fan 2 (and 4) (see 
).
Figure 30: System fan 1 and system fan 1&3
The standard system fan 1 is shorter and has just one fan cable; the redundant 
system fan 1&3 is taller (as 2 fans are integrated internally) and has two fan 
cables.
The procedure for installing and removing both system fans is identical except 
for connecting the fan cables.