Fujitsu C122-H007-01EN User Manual

Page of 58
CHAPTER 1 Installation Data 
1.3 Installation Specifications 
C122-H007-01EN 
 
1.3.2  Installation Specifications (PRIMEQUEST 2800E) 
TABLE 1.3 Installation Specifications (PRIMEQUEST 2800E) 
Items 
Contents 
Dimensions  
[mm (in.)] 
Width 
445(17.52) 
Depth (*1) 
782(30.79) 
Length 
 
438(17.25) 10U 
Mass [kg (lb)] (*2) 
150(331) 
Conditions for 
air conditioner 
Max. calorific 
value 
[kJ/h (BTU/h)] 
Interruptible power source 
17,712(16,787) 
High efficiency power supply (*13) 
17,388(16,480) 
Displacement 
[m3/min (ft
3
/min)] 
(*3) 
Recommended environmental 
temperature 
12(424) 
Max. 
28(989) 
Temperature and 
Humidity 
conditions (*4) 
At the time 
of operation 
Temperature [°C (°F)]] 
(*5) 
Humidity [%RH] 
20 to 80 
Max wet bulb 
temperature [°C (°F)]] 
29 (84.2) 
Downtime 
(*6) 
Temperature [°C (°F)]] 
0 to 50 (32 to 122) 
Humidity [%RH] 
8 to 80 
Max wet bulb 
temperature [°C (°F)]] 
29 (84.2) 
Noise [dB] (*7, *8) 
60 
Acoustic power level [B] (*8) 
7.8 
Permissible 
Vibration [m/s
2
 
(gal)] 
At the time of operation (Including 
standby) 
4.0 (400) (Composite seismic 
wave) 
Downtime (*9) 
10.0 (1000) (Composite 
seismic wave) 
Permissible dust level [mg/m
3
0.15 
Power supply 
conditions 
Input voltage and source resultant pulse number 
200 to 240 VAC±10 % 
1φ 
Frequency and fluctuating Range 
50/60 Hz + 2/-4% 
Max power 
consumption / 
apparent power 
At the time 
of operation 
Interruptible power 
source (*13) 
6.11 kW/6.43 kVA 
High efficiency power 
supply (*13) 
5.92 kW/6.23 kVA 
Downtime 
0.084 kW 
 
 
Power factor (*10) 
 0.95 or more 
Inrush current [A] [Rush hours] (*11) 
 20 or less 
Leak current [mA] (*12) 
 6.9 or less 
 
*1: Dimensions without protrusions (832 mm(32.76in) including front cover) 
*2: Numeric value when each optional device is mounted for maximum number of options. 
However, rail for mounting rack (5.7kg) and cable type are not included. 
Mass as per the installation configuration can be calculated using formula as shown below. 
Device mass = 78 + (11.1 * A) + (2.5 * B) + (1.8 * C) + (3.3 * D) [kg] 
A = Number of mounted SB (Minimum 1 to Maximum 4) 
B= Number of mounted IOU (Minimum 1 to Maximum 4) 
C= Number of mounted PSU (Minimum 2 to Maximum 6) 
D= Number of mounted DU (Minimum 0 to Maximum 2)*3: There are cases when device is overloaded or 
when abnormality is detected, FAN rotates at high-speed even if recommended environmental 
temperature is used. 
*4: Protect from condensation. 
*5: Temperature condition changes according to the installation location above sea level. 
For 0 to 1000 m (0 to 3281 ft) above sea level, temperature range at the time of installation: 5 to 35°C 
(41 to 95°F) 
For 1000 to 1500 m (3281 to 4921 ft) above sea level, temperature range at the time of installation: 5 to 
33°C (41 to 91.4°F) 
For 1500 to 2000 m (4921 to 6562 ft) above sea level, temperature range at the time of installation: 5 to 
31°C (41 to 87.8°F)