Fujitsu C122-H007-01EN User Manual

Page of 58
CHAPTER 1 Installation Data 
1.3 Installation Specifications 
12 
C122-H007-01EN 
 
1.3.4  Installation Specifications (PCI_Box) 
TABLE 1.5 Installation Specifications (PCI_Box) 
Item 
Contents 
Dimensions 
[mm (in)] 
Width 
482 (18.98) 
Depth 
740 (29.13) 
Length 
175 (6.89) 4U 
Mass [kg (lb)] (*2) 
35 (77) 
Conditions 
for air 
conditioner 
Max. calorific value [kJ/h (BTU/h)] 
1656 (1570) 
Displacement [m3/min 
(ft
3
/min)] (*3) 
FAN low speed (Low) 
3 (106) 
FAN medium speed (Normal) 
4 (141) 
FAN high speed (High) 
5 (177) 
Temperature 
and Humidity 
condition (*4) 
At time of 
operation 
Temperature [°C (°F)]] 
(*5) 
Humidity [%RH]] 
20 to 80 
Max wet bulb temperature [°C 
(°F)]] 
29 (84.2) 
 
Downtime 
(*6) 
Temperature [°C (°F)]] 
0 to 50 (32 to 122) 
Humidity [%RH]] 
8 to 80 
Max wet bulb temperature [°C 
(°F)]] 
29 (84.2) 
Noise [dB] (*7, *8) 
(Included in 
installation) 
Acoustic power level [B] (*8) 
(Included in 
installation) 
Permissibl
e Vibration 
[m/s
2
 
(gal)] 
At the time of operation (Including standby) 
4.0 (400) (Composite 
seismic wave) 
Downtime (*9) 
10.0 (1000) 
(Composite seismic 
wave) 
Permissible dust level [mg/m
3
0.15 
Power 
Supply 
conditions 
Input voltage and source resultant pulse number 
200 to 240 VAC±10 % 
100 to 120 VAC±10 % 
1φ 
Frequency and fluctuating Range 
50/60 Hz + 2/-4% 
Max 
power 
consumpti
on / 
apparent 
power 
At the time of 
operation 
Input voltage: 200 V 
450W/475 VA 
Input voltage: 100 V 
460W/485 VA 
Downtime 
Input voltage: 200 V 
10W/40VA 
Input voltage: 100 V 
10W/35 VA 
Power factor (*10) 
More than equal to 
0.95 
Inrush current [A] [Rush hours] (*11) 
Less than or equal to 
25 
Leak current [mA] (*12) 
Less than or equal to 
3.5 
*1: Dimensions without protrusions. 
*2: Numeric value when each optional device is mounted for maximum number of options. 
*3: If the device is overloaded or if abnormality is detected even though the recommended environmental 
temperature is used, the FAN rotates at high-speed. 
*4: Protect from condensation. 
*5: Temperature condition changes according to the installation location above sea level. 
For 0 to 1000 m (0 to 3281 ft) above sea level, temperature range at the time of installation: 5 to 35°C 
(41 to 95°F) 
For 1000 to 1500 m (3281 to 4921 ft) above sea level, temperature range at the time of installation: 5 to 
33°C (41 to 91.4°F) 
For 1500 to 2000 m (4921 to 6562 ft) above sea level, temperature range at the time of installation: 5 to 
31°C (41 to 87.8°F) 
For 2000 to 3000 m (6562 to 9843 ft) above sea level, temperature range at the time of installation: 5 to 
29°C (41 to 84.2°F) 
Error of + 100m in the sea level settings of the location of installation is permissible. 
*6: Downtime is the condition in which the device is packed and maintained.