Fujitsu C122-H007-01EN User Manual

Page of 58
CHAPTER 2 Connected Information 
2.3 Power cable connection 
24 
C122-H007-01EN 
 
200 V Redundant Power Feed Configuration (with single power feed, redundant power 
feed) with Power Distribution Box Connection 
It is necessary to arrange three PSUs, three FANUs, three Power cables (200 V IEC60320 C20) and two 
power distribution box (200 V IEC60320 C19×3type) for of 200 V Redundant Power Feed Configuration 
(single power feed, redundant power feed). 
When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution 
panel. See “
.” 
 
FIGURE 2.16 200 V Redundant Power Feed Configuration (single power feed, redundant power feed) with 
Power Distribution Box Connection 
 
Number 
Description 
(1) 
Power distribution box (200V C 19 
 3 type) 
 
200V Dual Power Feed Configuration with Power Distribution Box Connection 
It is necessary to arrange four PSUs, two FANUs, four power cables (200 V IEC60320 C20) and two power 
distribution box (200 V IEC60320 C19×3type) for 200 V dual power feed configuration for Japan and 
Overseas.  
When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution 
panel. See “
.” 
 
FIGURE 2.17 200 V Dual Power Feed Configuration with Power Distribution Box Connection 
 
Number 
Description 
(1) 
Power distribution box (200V C 19 
 3 type)