Fujitsu C122-H007-01EN User Manual

Page of 58
Appendix A Racks 
A.1 Rack Mounting 
35 
C122-H007-01EN 
 
 
Appendix A Racks 
This appendix provides various information on the mounting racks for the PRIMEQUEST 2000 series and 
PCI_Box. 
A.1 Rack Mounting 
The PRIMEQUEST 2000 series (including peripheral devices) has been developed and its operation 
guaranteed with the basic assumption that it is mounted in a Fujitsu rack. For safe use of a unit mounted in a 
Fujitsu rack, contact the distributor where you purchased your product, or your sales representative. 
When mounting the PRIMEQUEST products in a rack manufactured by another company, customers need 
to confirm on their own responsibility that the rack meets the PRIMEQUEST product specifications and 
requirements. 
See 
. 
A.2 Rack Mounting Requirements 
This section describes rack mounting requirements. 
A.2.1 Requirements for mounting in a Fujitsu 19-inch rack 
This section explains the requirements for mounting in a Fujitsu 19-inch rack. For safe use of the 
PRIMEQUEST 2000 series server mounted in a Fujitsu 19-inch rack, observe the mounting requirements 
described below. 
Recommended racks for mounting 
The following table lists the recommended racks for mounting the PRIMEQUEST 2000 series server and 
PCI_Box. 
TABLE A.1 Recommended racks for mounting 
Fujitsu 19-inch rack 
Depth (mm) 
Open area ratio 
Model 2742 
1,050 
80% 
Model 2737 
1,050 
80% 
Model 2724 
1,050 
80% 
Model 2642 
1,050 
80% 
Model 2624 
1,050 
80% 
Model 2616 
1,050 
75% 
PCR M1 742S 
1,050 
80% 
PCR M1 724S 
1,050 
80% 
PCR M1 642S 
1,050 
75% 
PCR M1 624S 
1,050 
75% 
PCR M1 616S 
1,050 
75% 
PCR M1 742A 
1,050 
80% 
PCR M1 724A 
1,050 
80% 
 
TABLE A.2 PRIMEQUEST 2000 series external dimensions 
Model 
Height 
Width 
Depth 
PRIMEQUEST 2000 series 
438 mm (10U) 
445 mm 
782 mm 
 
Note 
The Fujitsu 19-inch rack comes with a blank panel covering the front of each empty space that has no 
mounted device. 
If warm exhaust air from the device circulates to the front of the rack and reenters the device, it may cause a 
temperature alarm and lead to a device failure. 
Be sure to use the blank panel to cover the front of an empty space that has no mounted device.