DEFINITY Enterprise Communications Server Release 8.2
Upgrades and Additions for R8r  
555-233-115  
Issue 1
April 2000
Multicarrier G2 Universal Module to R8r EPN 
5-91
Critical Reliability 
5
Interconnect Port Networks 
 Critical Reliability 
Fiber optic cabling terminated to 9823A lightwave transceivers can interconnect 
PNs up to 4,900 feet (1493 m) apart. Fiber optic cabling terminated to 9823B 
lightwave transceivers can interconnect PNs up to 25,000 feet (7620 m) apart.
NOTE:
These distance limits are approximate measurements of the 
actual fiber 
right-of-way (not of the shortest linear distance) between the 2 endpoints.
NOTE:
It is important to label every cable that you install.
NOTE:
Keep track of which fiber attaches to which connector on each lightwave 
transceiver. This section provides figures offering the suggested way of 
making these connections.
The connectors on the lightwave transceivers are labeled either “TX” 
(transmit) or “RX” (receive), while the fibers attached to each connector are 
numbered either “1” or “2.” A viable fiber connection is only made when 
both fibers in each cable (“1” and “2”) route from the “TX” connector of a 
port network to the “RX” connector of its adjacent port network. For an 
example, refer to 
.
NOTE:
When finished, refer to 
 to 
administer the fiber links.
Collocated Port Networks
For a critical reliability system with 1 collocated EPN, use 2 fiber optic cables and 
4 lightwave transceivers to directly connect the networks. For a critical reliability 
system with 2 collocated EPNs, use 6 fiber optic cables and 12 lightwave 
transceivers to directly connect the networks.
NOTE:
Based on floor-plan considerations, the length of these cables may vary. 
Twenty-foot (6.1 m) cables are normally adequate for a Release 8 with 2 
port networks.
For collocated cabinets, the fiber optic cables should be routed directly from the 
PPN to the EPN cabinet. If a “DEFINITY style” PPN cabinet is collocated with 
another “DEFINITY style” EPN cabinet, route the cables 
up the cable tray and out 
the top of the PPN cabinet. The cables are then run to the other cabinet, through 
the top of the cabinet, and down the cable tray to the desired carrier level.
If a “DEFINITY style” PPN cabinet is collocated with either a small cabinet, 
medium cabinet, or single-carrier cabinet stack, route the cables 
down the cable 
tray and out the bottom of the PPN cabinet. The cables are then run to the EPN 
cabinet and up the outside of the rear panels to the desired carrier level.