DEFINITY Enterprise Communications Server Release 8.2
Upgrades and Additions for R8r  
555-233-115  
Issue 1
April 2000
Adding or Removing Cabinet Hardware 
6-40
Remove an EPN Cabinet from an Existing System 
6
9. Type 
change system-parameters features
 and press 
Enter
. Use this 
screen to change the TTI field back to its previous value before the 
upgrade.
10. When finished, place dust covers over all exposed fiber couplings that 
remain after the fiber optic cables are removed.
11. If any fiber optic cables were removed from Lightguide Interconnect Units 
(LIUs) or Fiber Patch Panels, remove the associated cable labeling. This 
will prevent confusion if existing fiber is later moved.
12. Return all unused equipment (not owned by the customer) to Lucent 
Technologies according to the requirements outlined in:
BCS/Material Logistics, MSL/Attended Stocking Locations
Methods and Procedures for Basic Material Returns
Troubleshooting 
Message Waiting Lamps On
This usually means that all affected port-related translations were not 
unadministered.
1. Type clear amw all <extension> and press 
Enter
. This clears the message 
waiting lamp for the specified extension.
2. Repeat the command for each extension with a lit message waiting lamp.