DEFINITY Enterprise Communications Server Release 8.2
Upgrades and Additions for R8r  
555-233-115  
Issue 1
April 2000
Upgrading R5si/R6si to R8r EPN and Adding Memory 
3-13
Release 5/6si to Release 8r 
3
Shut Down DEFINITY LAN Gateway System
!
WARNING:
Neglecting to shut down a DEFINITY LAN Gateway assembly before 
powering down the system cabinet can damage the LAN Gateway disk.
1. Log onto the DEFINITY LAN Gateway. See the 
DEFINITY Communications 
System Generic 3 Installation, Administration and Maintenance of 
CallVisor ASAI over the DEFINITY LAN Gateway for the procedure to log 
on.
2. When the main menu appears, select 
Maintenance.
3. Select 
Reset System from the Maintenance menu.
4. Select 
Shutdown from the Reset System menu.
5. Unseat the LAN Gateway assembly from its backplane connectors.
Shut Down DEFINITY AUDIX System
1. If a DEFINITY AUDIX System resides in the system to be upgraded, shut 
down the AUDIX assembly and allow the disk to completely spin down. 
Refer to the 
 at the end of this 
chapter.
!
WARNING:
Neglecting to shut down an AUDIX assembly before powering down 
the system cabinet where it resides can damage the AUDIX disk.
2. Unseat the AUDIX assembly from its backplane connectors.
Power Down Existing System
1. At each PPN cabinet power supply, set the main circuit breaker to OFF.
!
CAUTION:
Powering down the PPN will cause important system data, such as 
BCMS data, records of queued ACD calls, Automatic Wakeup 
requests, and Do Not Disturb requests to be lost. Refer to DEFINITY 
Enterprise Communications Server Release 8 Maintenance for R8r, 
for information about preparing the system for a power down.
2. At each EPN cabinet power supply, set the main circuit breaker to OFF.