Amtrol SPT-35 User Manual

Page of 4
Description
Standard Construction
Shell
Steel
Bladder
Heavy Duty Butyl 
NSF/ANSI 61
Bladder Thickness
.100 Minimum
System Connection Steel - ANSI Flange
Coating
Red Oxide Primer
Factory Precharge
25 PSIG (1.7 bar)
Use:
SG  =  Specific gravity of fluid: 
Water 1 
 
   
Ethylene glycol 1.1 
 
   
Propylene glycol 1.1 
 
   
Glycerin 1.3
Qs  =  Fire pump flow rate in gpm
Qss =  Fire pump flow rate in feet per second
=  Length of pipe in feet
=  Speed of pressure wave 
 
  in feet per second: 
Steel pipe 4500 ft/sec 
 
   
Cast iron = 4500 ft/sec 
 
   
Ductile iron 4500 ft/sec 
 
   
PVC pipe = 1250 ft/sec
P
2
  =  Maximum allowable pressure
P
1
  =  Tank pre-charge pressure setting
=  Gas constant (pre-charge gas) dry air 1.2
 
   
       nitrogen 1.4
A  =  Area of Pipe - pipe size
=  Velocity of water in feet per second
Precise Sizing For Pump Start-up:
Volume of Tank in Cubic Feet  =
SG x 2 x Qs x L
 ) ( 
P
2
 + 14.7
 )
1
/n 
 
 
449a  
      P
1  
+ 14.7 
 
 
 
P
2
 + 14.7
 )
1
/n
 
 
 
    P
1  
+ 14.7
 
 
 
-1
NOTE: Set pre-charge pressure 15% below static pressure.
NOTE: To convert cubic feet to gallons multiply by 7.481.
SIZING THE SURGE-TROL
 
              Tank                       A 
                 B   
Sys. 
E            Ship 
 
              Vol.                       Height                  Diameter 
Conn.  Conn.  Conn.  Stand           Wt. 
  Model 
 
 
 
 
 
 
 
Inset CtrLine  Dia 
 
No. 
Lit. 
Gal 
mm 
ins. 
mm 
ins. 
ins. 
ins.  ins. 
ins. 
kg 
lbs.
  SPT-7  200 
53  1245  48
7
/
8
 
610 
24 
1
9
/
16
  8
3
/
16
  19  166  367
 SPT-11  300 
80  1600  62
7
/
8
 
610 
24 
1
9
/
16
  8
3
/
16
  19  208  459
 SPT-14  400  106  1956  76
7
/
8
 
610 
24 
1
9
/
16
  8
3
/
16
  19  282  618
 SPT-18  500  132  2311  90
7
/
8
 
610 
24 
1
9
/
16
  8
3
/
16
  19  333  731
 SPT-21  600  158  1893  74
11
/
16
  762 
30 
1
3
/
8
  7
1
/
4
  24  433  950
 SPT-28  800  211  2365  93
1
/
8
 
762 
30 
1
3
/
8
  7
1
/
4
  24  513  1125
 SPT-35  1000  264  2086  82
1
/
8
 
914 
36 
3
1
/
4
  7
1
/
2
  30  693  1520
 SPT-42  1200  317  2465  94
1
/
2
 
914 
36 
3
1
/
4
  7
1
/
2
  30  784  1720
 SPT-50  1400  370  2781  109
1
/
2
  914 
36 
3
1
/
4
  7
1
/
2
  30  866  1900
 SPT-56  1600  422  2178  85
3
/
4
  1220  48 
1
3
/
4
  10
7
/
8
  42  1049  2300
 SPT-70  2000  528  2528  99
5
/
8
  1220  48 
1
3
/
4
  10
7
/
8
  42  1231  2700
Precise Sizing For Pump Shut-down:
Volume of Tank in Gallons =   Vv 
 
 
 
AF
AF - Acceptance Factor = 
1 - 
P
1
 + 14.7
)
1
/n
 
 
 
 
         P
2  
+ 14.7
Vv - Vacuum Volume  =   Qss x Tc x 7.481
Tc - Critical Time in seconds =  
2L
 
 
 
 
    a
NOTE: Set pre-charge pressure 50% below 
static pressure.
Precise Sizing Example 
For Pump Shut-down Based On:
Pump = 100 GPM
Pipe = 2” Steel Pipe; 1000 ft of pipe
Static Pressure = 100 psig
Max. Pressure = 150 psig
Pre-charge Gas = Dry Air
Tc  =  
2L  =  2(1000)  =  2000   =  .444
 
 
   a          4500        4500
Vv  =  Qss x Tc x 7.481  =  9.5 x .444 x 7.481  =  31.55
AF  = 
1 - 
P
1
 + 14.7
)
1
/n  = 
1 - 
64.7  
)
1
/
1.2
   =  .54
 
 
 
         P
2  
+ 14.7    
        164.7
Volume of Tank in Gallons =   Vv     =  31.55  =  58.4 
 
 
 
AF 
.54
Recommendation = SPT-11