Read, understand and follow ALL safety instructions
contained in this manual. Failure to follow safety
instructions and warnings could result in equipment
damage, serious injury, or death.
Connection to the branch circuit (mains) must be
performed by a licensed electrician.
The UPS contains internal batteries and may present a shock
hazard even when disconnected from the branch circuit
(mains). Before installing or servicing the equipment, ensure
that the system enable switch and input circuit breaker are set
to stand-by (OFF), that internal battery modules are removed,
that external extended run batteries are disconnected and the
branch circuit (mains) is disconnected.
q
q
q
The protective earth conductor for the UPS carries the
leakage current from the load devices (computer
equipment). An insulated grounding conductor that is
identical in size, insulation material, and thickness to the
grounded and ungrounded branch-circuit supply
conductors, except that it is green with or without a yellow
stripe is to be installed as part of the branch circuit that
supplies the UPS.
The grounding conductor described above is to be
grounded to earth at the service equipment, or if supplied
by a separately derived system, at the supply transformer
or motor-generator set.
The attachment-plug receptacles near the unit or
subsystem are all to be of a grounding type, and the
grounding conductors serving these receptacles are to be
connected to earth ground at the service equipment.
q
q
q
Each battery module is a 120 V, 7.2 Ah battery pack. There
is a risk of energy hazard. Before installing or replacing
battery nodules, remove jewelry such as wristwatches and
rings. High short -circuit current through conductive
materials could cause severe burns.
Do not dispose of batteries in a fire. The batteries may
explode.
Do not open or mutilate batteries. Released electrolyte is
harmful to the skin and eyes, and may be toxic.
Do not lift heavy loads without assistance
.
q
q
q
Ensure that battery module(s) are in the battery disconnect
position if they are in storage for an extended period of
time.
Store the battery module(s) at a cool ambient temperature
of < 25 °C.
Storage of batteries longer than six months without
recharging may result in permanent damage.
Electrical
Hazard
Electrical
Hazard
Electrical
Hazard
Electrical
Hazard
Electrical
Hazard
Caution
Note
!
Note
!
Safety Instructions
Handling Safety
<40 lb.
<18 kg
40–70 lb
18–32 kg
70–120 lb
32–54 kg
>120 lb
>54 kg
This equipment is intended for installation in a temperature-
controlled indoor area free of conductive contaminants. Refer
to Specifications at the APC web site for the actual
temperature range.
q
q
q
To comply with FAA regulations, the battery modules are
shipped disconnected to the UPS.
Batteries are recyclable. Used batteries can be sent to APC
for recycling or delivered to a recycling facility.
Only use APC batteries when adding or replacing battery
modules in the UPS.
General Equipment Safety
Deenergizing Safety
Electrical Safety
Battery Safety
Read and understand this manual before installing, operating or maintaining
APC equipment.
This manual provides important safety instructions and general information pertaining
to the Symmetra LX tower and rack-mount UPS and optional Extended Run Cabinet.
Illustrations are representative. Your Symmetra LX configuration, including
components and optional APC equipment, may be different from the models shown in
this guide.
Entire contents copyright 2003 by American Power Conversion Corporation. All rights
reserved. Reproduction in whole or in part without permission is prohibited. APC ,
PowerChute , InfraStruXure , Smart-UPS and Symmetra are registered trademarks
of American Power Conversion Corporation. All other trademarks are the property of
their respective owners.
®
®
©
®
®
®
®
®
Symmetra LX
Rack-mount UPS
®
Symmetra LX
Rack-mount
Extended Run
®
Symmetra LX
Tower Extended Run
®
Symmetra LX
Tower UPS
®
Symmetra LX
Safety Instructions and
General Information Guide
200/208/230 V, 4–16 kVA
Symmetra LX
Safety Instructions and
General Information Guide
200/208/230 V, 4–16 kVA
®
®
Important Safety and Installation Instructions
990-1602, English, December 2003
Verify that all branch circuit (mains) and low voltage (control)
circuits are de-energized, and locked out before installing
cables or making connections, whether in the junction box or to
the UPS.
q
q
q
q
q
Wiring by a qualified electrician is required.
Check national and local codes before wiring.
Strain relief is required for all hardwiring.
All openings in the rear of the UPS must be covered. Failure
to do so may result in personal injury of equipment damage.
Select wire size and connectors according to national and
local codes.
Electrical
Hazard
Caution
Note
!
Hardwiring Safety
q
q
q
Loads can be connected directly to the UPS using the output
plugs on the PDU panel. Ensure that the total load being
plugged into a PDU panel DOES NOT EXCEED the branch
circuit breaker rating on the PDU panel.
Do not install a PDU panel when a PDU warning label is
present.
Use flexible metal conduit to make maintenance and service
easier.