Appendix I
Trouble Shooting
SYMPTOMS
POSSIBLE CAUSES
SOLUTIONS
Inside air is too dry
Over ventilation - speed setting
Adjust speed setting
too high
Dehumidistat setting is too low
Set dehumidistat control in a
higher position (if applicable)
Persistent condensation on
Improper adjustment of
Adjust dehumidistat control knob
windows, walls, ceilings, etc.
dehumidistat control
to a lower setting
Improper ventilation rate
Install a dehumidistat (option)
Window frame is too cold or leaky
Repair window frame
Unit stops functioning
Electrical supply interrupted
Check the unit circuit breaker
Air from supply diffusers too cold Imbalance of supply and exhaust air
Check filters and cores for blockage
Check balance of airflows
Outdoor temperature very cold
Install electric duct heater
if necessary
Unit makes annoying noise
Blower wheel out of alignment
Remove the motor/blower
assembly and adjust blower wheel
Heat exchange core freezing up
Imbalance of supply and exhaust air
Check filters and cores for blockage
Check balance of airflows
Defrost damper not functioning
Check for operation of both
defrost damper actuators