EMI Volts/HZ/pH User Manual

Page of 28
www.enviromaster.com
Side Discharge Condensers
4
itemS For ConSiDeration
• Locate the unit as close to the indoor 
section  as  possible.  (See  Tubing 
Specifications chart on pape 7.)
• If the unit is used for low ambient cool-
ing down to 32°F, this option must be 
specified to prevent system damage.
• Avoid high traffic areas and prevailing 
wind locations.
• Surface must be flat and level.
•  Mount  unit  above  typical  snow  fall 
levels.
Ensure free flow of air through the unit. 
Air must not recirculate from discharge to 
intake.  Air is drawn through the coil and 
side discharged through the fan grille. 
minimum 48" clearance is necessary for 
the  condenser  discharge.  rear  intake 
(coil  side)  clearance  is  12"  minimum. 
Consider how power will be run to the unit 
from the power source. Refrigerant piping 
should be a direct line to the indoor unit.
  Site preparation 
1. Place the unit on a flat concrete surface 
or pad if on the ground. Roof mounting 
should use a build up platform to avoid 
intake of hot air from the roof.
2. In areas of heavy snowfall, condens-
ers should be set above the level of 
maximum anticipated snowfall (12" 
is usually adequate).
1. Loosen the screws on left and right sides 
of the front panel. (Do not remove these 
screws.)
2. Remove the screws on the front of the 
panel. 
3. T
o remove front panel:
4. S
lide front panel forward to clear side 
screws and remove. 
inStallation inStrUCtionS
inStallation inStrUCtionS
S1C is shown
Unit moUnting inStrUCtionS
Side discharge unit   allows for per-
manent mounting through the feet. This is 
highly recommended due to the vertical 
design of the unit
.
SYStem optionS (cont.)
void the warranty. A Field Installed Low-
Ambient kit
 is good for operation down to 
32º F. This is accomplished by cycling the 
condenser fan on and off, which will in turn 
maintain a constant low side pressure pro-
viding a steady cooling effect and keeping 
the air handler from frosting-up.