Emerson I-0021 User Manual

Page of 238
5 - 46
NGA 2000
90003482(2) [NGA-e (MLT-Software 3.2.X)] 07/98
In the following table you can see which types of operators and operands you can use:
Operator types
Operator Description
-1
ADD
Add Operand to IR (intermediate result)
-2
SUB
Subtract Operand from  IR
-3
DIV
Divide IR by operand
-4
MUL
Multiply IR with operand
-5
ADDC c
Add Constant to IR
-6
SUBC c
Subtract constant from IR
-7
DIVC c
Divide IR by constant
-8
MULC c
Multiply IR with constant
-9
ADDM m
Add Memory to IR
-10
SUBM m
Subtract Memory from IR
-11
DIVM m
Divide IR by memory
-12
MULM m
Multiply IR with memory
-13
STOM m
Store IR at memory and set IR = 0.0
-14
STOR r
Store IR  to result  and set IR=0.0
-15
NOP
No operation
-16
ABS
Convert IR into absolute value
-17
EOP
End of program
Operand Types
Operand Description
1
Calculator Result #1
2
Calculator Result #2
3
Calculator Result #3
4
Calculator Result #4
5
Concentration
Channel 1 (PPM!)
6
Concentration average
Channel 1 (PPM!)
7
Temperature
Channel 1
8
Pressure
Channel 1
9
Flow
Channel 1
10
Concentration
Channel 2 (PPM!)
11
Concentration average
Channel 2 (PPM!)
12
Temperature
Channel 2
13
Pressure
Channel 2
14
Flow
Channel 2
15
Concentration
Channel 3 (PPM!)
16
Concentration average
Channel 3 (PPM!)
17
Temperature
Channel 3
18
Pressure
Channel 3
19
Flow
Channel 3
20
Concentration
Channel 4 (PPM!)
21
Concentration average
Channel 4 (PPM!)
22
Temperature
Channel 4
23
Pressure
Channel 4
24
Flow
Channel 4
25
Concentration
Channel 5 (PPM!)
26
Concentration average
Channel 5 (PPM!)
27
Temperature
Channel 5
28
Pressure
Channel 5
29
Flow
Channel 5