Sterling 882.93092.01 User Manual

Page of 90
GP Series Portable Chillers 
Chapter 2: Functional Description 
11 of 90 
Air-Cooled Condenser – Aluminum fin/ tube with washable filters, packaged units only. 
Variable speed fan control standard for all remote air cooled condensers and GPAC70 
through 210.  Optional on GPAC20 through 50. 
Water-Cooled Condenser – Tube-in-tube condensers (GPWC20 – GPWC50), Shell-and-
tube condensers (GPWC70 – GPWC210).  All come with electronic cooling water regulating 
valves. 
Remote Air-Cooled Condenser– Aluminum fin/tube with low ambient control down to  
–20ºF (-29ºC) via variable-speed fan(s). 
Reservoir – GP20 and GP30 models use a 20 gallon (75 liter) polyethylene tank, GP40 and 
GP50 models use a 40 gallon (150 liter) polyethylene tank, GP70 thru GP105 models use a 
70 gallon (265 liter) polyethylene tank, GP140 thru GP210 models use a 140 gallon (530 
liter) polyethylene tank.  304SS is available as an option for all sizes.  
Piping – 
Non-ferrous chilled water piping  
Pump – ODP motors (TEFC Optional)—horizontally mounted stamped stainless steel 
construction. 
Other Mechanical Features 

  Low process water thermal flow switch 

  NEMA-rated fan motor(s) on air-cooled models 

  Galvanized structural steel frame, polyester powder coat painted cabinetry  

  Internal process water bypass valve for system protection only 

  Fully insulated refrigeration and process water piping 

  20 mesh Y strainer on process water piping into the evaporator 

  Tank level indication via operator interface 

  Pump pressure indication via operator interface 
Electrical Features 

  Fully accessible NEMA 4/12-style electrical control enclosure  

  Single-point power and ground connection 

  Non-fused disconnect switch, lockable 

  Branch circuit protection 

  208-230/3/60, 460/3/60, 575/3/60 volt; 400/3/50 volt 
Refrigeration Features 

  HFC-410a refrigerant 

  Electronic modulating hot gas bypass capacity control 

  High refrigerant pressure cutout switch (manual reset) 

  Suction and discharge pressure transducers. 

  High refrigerant pressure spring actuated relief valve