GP Series Portable Chillers 
Chapter 4: Operation 
46 of 90 
Variable 
Description 
Access Level 
Operator 
Supervisor 
Analog Out 3 
Determines how analog output 3 is used.  It can be 
set to CHIL IN (retransmission of the chiller in 
temperature), CHIL OUT (retransmission of the 
chiller out temperature), FROM PROC 
(retransmission of the from process temperature) or 
TO PROC (retransmission of the to process 
temperature). 
 
Analog Out 4 
Determines how analog output 4 is used.  It can be 
set to CHIL IN (retransmission of the chiller in 
temperature), CHIL OUT (retransmission of the 
chiller out temperature), FROM PROC 
(retransmission of the from process temperature) or 
TO PROC (retransmission of the to process 
temperature). 
 
Digital In 8 
Determines how digital input 8 is used. It can be set 
to START/STOP (remote start stop), NO 
WARNING (normally open warning alarm), NC 
WARNING (normally closed warning alarm), NO 
FAULT (normally open fault alarm), NC Fault 
(normally closed fault), PHASE MNTR (power 
phase monitor), TMP SAFETY (high temp safety) 
 
Start Mode 
When Digital In 8 is configured to START/STOP 
this determines if the chiller’s online status is 
determined by the button on the display (LOCAL) or 
digital input 8 (REMOTE). 
 
Chil Cntl Sens 
Determines which sensor is used to control the 
chiller.  It can be set to CHIL OUT (chiller out 
temperature), CHIL IN (chiller in temperature), TO 
PROC (to process temperature) or FRM PROC 
(from process temperature). 
 
Proc Cntl Sens 
Determines which sensor is used to control the 
process loop.  It can be set to TO PROC (to process 
temperature) or FRM PROC (from process 
temperature). 
 
Pump 2 OL Alm 
When set to CRIT, the pump 2 overload alarm will 
deactivate compressors and pumps.  When set to 
WARN, compressors and pumps are allowed to 
continue to run when the pump 2 overload alarm 
occurs. 
 
Flow 2 Alm Type 
When set to CRIT, the flow 2 alarm will deactivate 
compressors and pumps.  When set to WARN, 
compressors and pumps are allowed to continue to 
run when the flow 2 alarm occurs. 
 
Alarm Out 
Determines when the alarm output is activated.  
When set to ALL ALARMS, the output is activated 
when any new alarm occurs.  When set to CRIT 
ALARMS, the output will only activate when 
critical alarms (those that force the pump or 
compressor off) occur. 
 
Network Prot 
Determines what network protocol is used for 
communications.  This can be set to BACNET485, 
BACNET IP, MODBUS485, MODBUS IP, LON or 
WEB. 
 
Network Baudrate 
Determines the baudrate for communications. 
 
Network Address 
Determines the network address of the chiller on the 
network. 
 
Units 
Determines if STANDARD (English) or METRIC 
units are used.