EMC and leakage currents
3
(3) Selection of rated sensitivity current of earth (ground) leakage breaker
When using the earth (ground) leakage circuit breaker with the inverter circuit, select its rated sensitivity current as
follows, independently of the PWM carrier frequency:
<Example>
z
Selection example (in the case of the left figure (400V class
 
 connection))
z
Inverter leakage current (with and without EMC filter)
Input power conditions
(200V class: 220V/60Hz, 400V class: 440V/60Hz, power supply unbalance within 3%)
⋅ Breaker designed for harmonic and surge suppression
Rated sensitivity current: 
I
Δn ≥ 10 × (Ig1 + Ign + Igi + Ig2 + Igm)
⋅ Standard breaker
Rated sensitivity current: 
I
Δn ≥ 10 × {Ig1 + Ign + Igi + 3 × (Ig2 + Igm)}
Ig1, Ig2: Leakage currents in wire path during commercial
power supply operation
Ign: Leakage current of inverter input side noise filter
Igm: Leakage current of motor during commercial power 
supply operation
Igi: Leakage current of inverter unit
Breaker Designed for 
Harmonic and Surge 
Suppression
Standard Breaker
Leakage current Ig1 (mA)
 
×
 
66 
×
5m
= 0.11
1000m
Leakage current Ign (mA)
0 (without noise filter)
Leakage current Igi (mA)
1 (without EMC filter)
Refer to the following table for the leakage 
current of the inverter*
Leakage current Ig2 (mA)
 
×
 
66 
×
60m
= 1.32
1000m
Motor leakage current Igm (mA)
0.36
Total leakage current (mA)
2.79
6.15
Rated sensitivity current (mA) 
(≥ Ig × 10)
30
100
Refer to page 15 for the EMC filter.
Voltage
(V)
EMC Filter
ON (mA)
OFF (mA)
200
22(1)*
1
400
30
1
400
1
1
*For the FR-A720-0.4K and 0.75K, the EMC filter is always valid.
The leakage current is 1mA.
CAUTION
⋅ Install the earth leakage breaker (ELB) on the input side of the inverter.
⋅ In the   connection earthed-neutral system, the sensitivity current is blunt against an earth (ground) fault in the inverter output
side. Earthing (Grounding) must conform to the requirements of national and local safety regulations and electrical codes. (NEC
section 250, IEC 536 class 1 and other applicable standards)
⋅ When the breaker is installed on the output side of the inverter, it may be unnecessarily operated by harmonics even if the
effective value is less than the rating. In this case, do not install the breaker since the eddy current and hysteresis loss will
increase, leading to temperature rise.
⋅ The following models are standard breakers....BV-C1, BC-V, NVB, NV-L, NV-G2N, NV-G3NA and NV-2F earth leakage relay
(except NV-ZHA), NV with AA neutral wire open-phase protection
The other models are designed for harmonic and surge suppression....NV-C/NV-S/MN series, NV30-FA, NV50-FA, BV-C2,
earth leakage alarm breaker (NF-Z), NV-ZHA, NV-H
(200V  60Hz)
(200V  60Hz)
1. 5 3. 7
2. 2
7. 5 1522
11
37
30
55
45
5.5
18. 5
0. 1
0. 2
0. 3
0. 5
0. 7
1. 0
2. 0
0
2 0
4 0
6 0
8 0
100
120
2 3.5
5.5
8 1422
30
38
60
80
100
150
Motor capacity (kW)
Example of leakage current of
cable path per 1km during the
commercial power supply operation
when the CV cable is routed in 
metal conduit
Leakage current example of
three-phase induction motor
during the commercial
power supply operation
Leakage currents (mA)
Leakage currents (mA)
Cable size (mm
2
)
Motor capacity (kW)
For "   " connection, the amount of leakage current is appox.1/3 of the above value.
(Three-phase three-wire delta
 connection 400V60Hz)
Example of leakage current per 1km during 
the commercial power supply operation 
when the CV cable is routed in metal conduit
Leakage current example of three-
phase induction motor during the 
commercial power supply operation
(Totally-enclosed fan-cooled
 type motor 400V60Hz)
0
2 0
4 0
6 0
8 0
100
120
leakage currents (mA)
leakage currents (mA)
2 3.5
5.5
8 1422
30
38
60
80
100
150
Cable size (mm
2
)
0. 1
0. 2
0. 3
0. 5
0. 7
1. 0
2. 0
1. 5 3. 7
2. 2
7. 5 1522
11
37
30
55
45
5.5
18. 5
Noise 
filter
Inverter
ELB
Ig1
Ign
Igi
Ig2
Igm
IM
5.5mm
×
 
5m
5.5mm
2  
×
 
60m
400V
2.2kW
3
φ
1
3
1
3
Phase 
grounding
Earthed-neutral 
system