Install and Cable the Cabinets 
Page 1-21
AC Power and Ground 
1
Install Coupled Bonding Conductor 
The Coupled Bonding Conductor (CBC) provides for mutual inductance coupling 
between the CBC and the telephone cables that are exposed to lightning. The 
conductor can be a 10 AWG (#25) (6 mm
2
) wire tie wrapped to the exposed 
cables, a metal cable shield around the exposed cables, or 6 spare pairs from 
the exposed cable. 
In a high rise building, connect the CBC to an approved building ground on each 
floor. To provide the coupled bonding protection:
1. Connect 1 end of the conductor to a telephone cable building entrance 
protector ground that is connected to an approved ground.
2. Route the rest of the conductor next to the exposed telephone cables 
being protected until they reach the cross-connect nearest to the 
telephone system.
3. Position the non-exposed telephone cables at least 12 inches (30.5 cm) 
away from exposed telephone cables whenever possible.
4. Terminate the other end to the single-point ground block provided for the 
telephone system.
Connect and Route Cabinet AC Power Cords
!
CAUTION:
The AC power cords may connect to a properly rated power distribution 
unit, individual AC power receptacles, or to a UPS. See 
1. Be sure the circuit breakers at the AC load center are 
OFF
2. Connect Cabinet A to an “unswitched” or “always on” electrical outlet.