Lucent Technologies 555-230-128 User Manual

Page of 144
DEFINITY Enterprise Communications Server Release 6
Installation and Test for Compact Modular Cabinets  
555-230-128  
Issue 3
May 1998
Install and Cable the Cabinets 
Page 1-26
Install Main Distribution Frame and External Modem 
1
Install Main Distribution Frame and 
External Modem 
Install the MDF
!
CAUTION:
The optional MDF is a special 110 cross-connect field and is smaller than standard 
110 cross-connect hardware. Do not install standard 110 hardware inside the right 
panel.
NOTE:
The depth of any equipment installed inside the right panel must not exceed 2.5 
inches (6.3 cm), otherwise the right cover panel cannot fit over the right panel.
The optional MDF represents the trunk/auxiliary field. 
1. Mount the optional MDF to the right panel. See 
. The MDF may 
be mounted at the top of the right panel in other cabinets, if desired. See 
Install the External Modem
The U.S. Robotics Model 839 external modem is the recommended external 
modem. Release 6 CMC systems operate with this modem set to the factory 
default settings. 
NOTE:
You may use a locally obtained, type-approved external modem (33.6 bps 
and V.34 protocol). Contact your Lucent Technologies representative for 
more information.
1. Use installer-provided hardware to mount the modem. See 
2. Route the MODEM cable (P2) from the Processor Interface Cable through 
the cable trough and to the modem.
3. Connect the cable to the modem. Refer to 
Pinout’’ on page 2-11
 for the pinout of the modem cable.
4. Plug the modem power cord into an electrical outlet and turn on the 
modem.
5. Modem setup and administration is performed in 
Settings’’ on page 1-98
.