Honeywell W7750A User Manual

Page of 116
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
51
74-2958—1
Fig. 42. LED location on W7750.
T7770C,D Wall Module Bypass Pushbutton and 
Override LED
Pressing the bypass pushbutton, located on the T7770C,D 
Wall Modules in Fig. 43, causes the override LED to display 
the Manual Override mode of the controller. The modes are:
Fig. 43. The T7770C,D Wall Modules LED and Bypass 
pushbutton locations.
1.
LED = Off. No override active.
2.
LED = Continuously on. Bypass mode (timed Occupied 
override).
3.
LED = One flash per second. Continuous Unoccupied 
override.
4.
LED = Two flashes per second. Remote only, continu-
ous Occupied override. 
T7560A,B Digital Wall Module Bypass Pushbutton 
and LCD Display Occupancy Symbols
See Fig. 44 for the T7560A,B Digital Wall Module bypass 
pushbutton location.
Press and release the bypass pushbutton, located on the 
T7560A,B Digital Wall Modules in Fig. 44 for more than one 
second to cause the sun symbol on the bottom right side of 
the LCD display to appear. Pressing the bypass pushbutton 
for more than four seconds causes the controller, hard-wired 
to the T7560A,B, to go into continuous unoccupied override. 
The T7560A,B displays the moon symbol.
Fig. 44. The T7560A,B Digital Wall Module Bypass 
pushbutton location.
APPENDICES
Appendix A. Using E-Vision to Commission a 
W7750 Controller.
NOTE:
When commissioning a CVAHU W7750 Controller, 
E-Vision first checks that the actual hardware model 
(such as W7750A,B,C) is the same type which was 
selected from the Application Selection/Output tab. If 
the types do not match, the download does not occur 
and the user-entered values in the Application 
Selection screens all revert back to default values.
Sensor Calibration
The space temperature, the optional resistive and voltage/
current (W7750B,C only) inputs can all be calibrated. The wall 
module setpoint potentiometer can not be calibrated.
Perform the sensor calibration by adding an offset value 
(either positive or negative) to the sensed value using 
E-Vision menus (see E-Vision user guide, form number 
74-2588).
When calibrating voltage/current sensors on the (W7750B,C), 
the offset amount entered by the user is in volts, regardless of 
the inputs actual engineering units. See Appendix E for 
information on how to derive the proper voltage value to enter 
as an offset during calibration.
Setting the Pid Parameters
The W7750 is designed to control a wide variety of 
mechanical systems in many types of buildings. With this 
flexibility, it is necessary to verify the stability of the 
temperature control in each different type of application. 
M10095A
W7750
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
J3
31
30
29
28 27 26 25
24 23 22 21
20
19 18 17 16
GND
LED
BYPASS SNSR
SET PT
AI-1 
OHM
A1-2 
OHM
AI-3 
V/mA
AI-4
V/mA
20VDC
OUT
DI-4
DI-3
DI-2
DI-1
VAC
24
VAC
24
COM
1
OUT
2
OUT
3
OUT
4
OUT
5
OUT
6
OUT
7
OUT
8
OUT
AI
GND
AI
GND
AI
GND
LONWORKS
-BUS
LON
JACK
DI
GND
DI
GND
STATUS
LED
M11617
T7770C
T7770D
OVERRIDE
LED
BYPASS
PUSHBUTTON
BYPASS
PUSHBUTTON
70
65
60
55
75
80
85
OVERRIDE
LED
M17500
BYPASS
PUSHBUTTON