Programming Manual - Basic & Applied Instruction Edition
4 Devices in Detail
4.9 Data Register and File Register [D]
4.9.4
Functions and operation examples of file registers
A file register is a device for setting the initial value of a data register with the same number.
Each file register stores 16-bit data (whose most significant bit specifies the positive or negative sign). Two file
registers combined can store 32-bit numeric data (whose most significant bit specifies the positive or negative sign).
Up to 7000 data registers starting from D1000 can be specified as file registers by the parameter setting.
The number of file registers varies depending on the model.
Refer to Subsection 2.7.3 for the file register setting range.
• In parameter settings, 1 to 14 blocks can be specified. One block secures 500 file registers, but uses the program 
memory area by 500 steps.
• When some of data registers starting from D1000 are specified as file registers, the remaining data registers not 
specified as file registers can be used as data registers.
This section explains how to handle file registers.
1. Operation of file registers
• The contents of the file register area [A] set inside the built-in memory or memory cassette are batch-transferred to 
the data memory area [B] inside the system RAM when the PLC power is turned ON or when the PLC mode 
switches from STOP to RUN.
When data registers are specified as file registers by the parameter setting, the contents of the file register area [A] 
inside the program memory are transferred when the PLC power is turned ON or when the PLC mode switches 
from STOP to RUN. This means that the contents changed in the data memory are initialized every time when the 
PLC turns ON or when the PLC mode switches from STOP to RUN.
When it is necessary to save data changed in the data memory using a sequence program, update the file register 
area [A] to the changed values by the same-number register update mode in BMOV 
(FNC 15) instruction described later.
• Difference between BMOV (FNC 15) instruction and other instructions
The table below shows the differences between the BMOV (FNC 15) instruction and other applied instructions.
The data stored in data registers set as file registers are automatically copied from the file register area [A] to the
data register area [B] when restoring the power.
• When a file register is monitored from peripheral equipment, the data register area [B] inside the data memory is 
read.
When "file register device current value change", "file register device forced reset" or "PLC memory all clear" is 
executed from peripheral equipment, the file register area [A] inside the program memory is changed, and then the 
data is automatically transferred to the data register area [B].
Accordingly, when file registers are to be overwritten, the program memory should be "built-in memory" or "memory 
cassette whose protect switch is set to OFF". (The memory cassette cannot be overwritten from peripheral 
equipment if its protect switch is set to ON.)
Instruction
Transferred contents
Remarks
BMOV instruction
Data can be read from and written to the file register
area [A] inside the program memory.
Applied
instructions other
than BMOV 
instruction
Data can be read from and written to the data
register area [B] inside the image memory in the
same way as general data registers.
Because the data register area [B] is provided inside the
system RAM in the PLC, its contents can be arbitrarily
changed without being limited by the optional memory
format.
Data register
[B]
Inside system
RAM
Inside built-in memory
or
memory cassette
Program
memory
Program/
comment
File register
[A]
D1000
500 points 
×
14 blocks
maximum
(7000 points
maximum)
When power
is turned ON
When PLC
mode is
changed
from STOP
to RUN
Data
memory
Data register
Data register
D7999
D1000
D 0
Read
Write
The remaining area can be used as data registers for general purpose.
For devices D1000 and later specified
as operands in applied instructions other
than BMOV (FNC 15) , indirectly
specified values for timers, counters or
devices in RST instructions can be read
from and written to the data register
area [B] in the same way as general
data registers.