7 Basic Instruction
7.9 MC, MCR
1
Introdu
ction
2
Ov
ervi
ew
3
Instruction 
Li
st
4
D
evices 
in Det
ai
l
5
Specifi
ed the
De
vice
 &
 
C
onst
ant
6
Bef
ore
 
Pr
og
ra
mmi
ng
7
Bas
ic 
Instruction
8
FN
C00-FN
C0
9
Program Fl
ow
9
FNC
10-FN
C19
Mov
e & Com
pare
10
FNC
20-FNC
29
Arith. & Lo
gi
Operati
on
2) When the nesting structure is adopted
When using MC instructions inside MC instruction, increase the nest level "N" in turn in the way "N0 
→ N1 → N2
→ N3 → N4 → N5 → N6 → N7".
For returning from the nesting structure, reset the nest levels from the highest one in turn using MCR instruction in
the way "N7 
→ N6 → N5 → N4 → N3 → N2 → N1 → N0".
For example, if "MCR N5" is programmed without programming "MCR N6" and "MCR N7", the nest level is
returned to 5 immediately.
Available nest levels are from N0 to N7 (eight layers).
[B]
[A]
[C]
[B]
While X000
is OFF
[A]
N 1
N 2
X000
MC
N  0
M100
 N 0
M100
X001
Y000
X002
MC
N  1
M101
 N 1
M101
X003
Y001
X004
MC
N  2
M102
 N 2
M102
X005
Y002
MCR
N  2
X006
Y003
MCR
N  1
X007
Y004
MCR
N  0
X010
Y005
N 0
N 1
N 2
N 0
[D]
[C]
While
X002 is
OFF
While
X004
is OFF
Circuit program
Level N0
The bus line B is active while X000 is ON.
Level N1
The bus line C is active while both X000 and
X002 are ON.
Level N2
The bus line D is active while all of X000,
X002 and X004 are ON.
Level N1
The bus line returns to the status of the bus
line C by "MCR N2".
Level N0
The bus line returns to the status of the bus
line B by "MCR N1".
Initial status
The bus line returns to the initial status of the
bus line A by "MCR N0".  Accordingly, Y005
turns ON or OFF by turning ON or OFF of
X010 regardless of X000, X002 and X004.