Mitsubishi Electronics FX3G User Manual

Page of 964
32
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series
Programming Manual - Basic & Applied Instruction Edition
2 Overview (Sequence Program)
2.5 Introduction of Devices Constructing PLC
8. Index registers (V)(Z)
→ Refer to Section 4.11.
Among registers, there are index type registers V
and Z used for modification.
A data register V or Z is added to another device as
follows:
[In the case of "V0, Z0 = 5"]
D100V0 = D105, C20Z0 = C25 
← Device number +
V  or Z  value 
Data registers and index registers are used for
indirectly specifying the set value of timers and
counters, or used in applied instructions.
9. Pointers (P)(I)
→ Refer to Section 4.12.
Pointers are classified into branch pointers and
interrupt pointers.
• A branch pointer (P) specifies the jump 
destination of the conditional jump CJ (FNC 00) or 
the call subroutine CALL (FNC 01) instruction.
• An interrupt pointer (I) specifies the routine of an 
input interrupt, timer interrupt or counter interrupt.
10.Constants (K)(H)(E)
→ Refer to Chapter 5.
Constant numerical values used in the PLC, "K"
indicates a decimal integer value, "H" indicates a
hexadecimal value, and "E" indicates a real number
(floating point data).
Constants are used as set values or present values
of timers and counters, or operands for applied
instructions.