13.8 FNC 57 – PLSY / Pulse Y Output
4. Handling of pulse output terminals in FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 series main units
The outputs Y000 and Y001 are the high-speed
response type.
When using a pulse output instruction or
positioning instruction, adjust the load current of
the open collector transistor output to about 10 to
100 mA (5 to 24V DC).
When the load is smaller, connect a dummy
resistor in parallel to the outside of a used output
terminal (Y000 or Y001) as shown in the circuit
diagram below so that the specified current
shown above flows in the output transistor.
5. Cautions on using special high-speed output adapters
1) Outputs of special high-speed output adapters work as differential line drivers.
2) Set the pulse output type setting switch in a special high-speed output adapter to the "pulse chain + direction"
(PLS DIR) side.
If the switch is set to the "forward rotation pulse chain reverse rotation pulse chain" (FP RP) side, normal
operations are disabled. The pulse output destination changes depending on the PLC output status as shown in
the table below.
3) Set the pulse output type setting switch while the PLC is stopped or while the power is OFF.
Do not manipulate the pulse output form setting switch while pulses are being output.
4) When special high-speed output adapters are connected, the same output numbers in the main unit are assigned
as shown in the table below.
Only wire the appropriate output terminals.
Outputs in special high-speed output adapters and the main unit operate as shown below.
Assignment of output numbers in special high-speed output adapters
Output operation
Pulse output 
destination
Output affecting 
operation
Operation
 = 
Y000
Y004
While Y004 is ON, pulses are output from Y000 in the high-speed output adapter.
While Y004 is OFF, pulses are output from Y004 in the high-speed output adapter.
 = 
Y001
Y005
While Y005 is ON, pulses are output from Y001 in the high-speed output adapter.
While Y005 is OFF, pulses are output from Y005 in the high-speed output adapter.
Status of output form setting 
switch
Signal name
Setting name in each 
positioning instruction
Output number
1st unit
2nd unit
1st axis
2nd axis 3rd axis
4th axis
"FP RP" side
Forward rotation pulse 
chain (FP)
Pulse output destination
Y000
Y001
Y002
Y003
Reverse rotation pulse 
chain (RP)
Rotation direction signal
Y004
Y005
Y006
Y007
"PLS DIR" side
Pulse chain
Pulse output destination
Y000
Y001
Y002
Y003
Direction
Rotation direction signal
Y004
Y005
Y006
Y007
Output operation
Relay output type/triac output type main
unit
While instruction is activated, relevant output is ON. (LED is also ON.)
Use a special high-speed adapter.
Special high-speed output adapter
Operated. (LED is also operated.)
Set the output frequency to "200kHz" or less.
Transistor output type main unit
Operated. (LED is ON.)
Set the output frequency to "100kHz" or less.
Item
Description
Operating voltage range
5 to 24V DC
Operating current range
10 to 100 mA
Output frequency
100 kHz or less
External
power
supply
Equipment
load
resistor
Dummy
resistor
Y000
COM1
PLC
(transistor output)
[sink output]
  D