Programming Manual - Basic & Applied Instruction Edition
14 Handy Instruction – FNC 60 to FNC 69
14.8 FNC 67 – RAMP / Ramp Variable Value
• After transfer is completed, the instruction execution complete flag M8029 turns ON, and the 
 value is 
returned to the 
 value.
• When acquiring the operation result at a constant time interval (constant scan mode)
Write a prescribed scan time (which is longer than the actual scan time) to D8039 and set M8039 to ON to select 
the constant scan mode in the PLC.
For example, when "20 ms" is written to D8039 and "n" is set to 100, the 
 value will change from 
 to 
 in 2 seconds.
2. Operation of the mode flag (M8026)
In FX
3U
/FX
3UC
 PLCs, the contents of  
 are changed as follows depending on the ON/OFF status of the mode
flag M8026.
In FX
3S
/FX
3G
/FX
3GC
 PLCs, the contents of 
 are same as the case "2) When M8026 is ON" below regardless of
the ON/OFF status of the mode flag M8026.
1) When M8026 is OFF
2) When M8026 is ON
Related devices
→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.
*1.
M8026 is available only in FX
3U
/FX
3UC
 PLCs, and is cleared when the PLC mode switches from RUN to
STOP.
Caution
1. When specifying a latched (battery backed) type device as 
When setting PLC to the RUN mode while the command input is ON, clear 
 in advance.
Device
Name
Description
M8029
Instruction
execution complete
Turns ON when 
 becomes equivalent to 
 after "n" operation cycles.
M8026
*1
RAMP mode
Refer to the operation of the mode flag M8026 described above.
  