Mitsubishi Electronics FX3G User Manual

Page of 964
40
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series
Programming Manual - Basic & Applied Instruction Edition
2 Overview (Sequence Program)
2.6 Program Memory and Devices
b) FX
3G
/FX
3GC
 PLCs
*1.
These registers can be changed from the general type to the latched (battery backed) type by the parameter
setting when the optional battery is installed.
*2.
Some devices are cleared when the PLC status switches from STOP to RUN.
→ For special data registers, refer to Chapter 37.
Item
Power OFF
Power 
OFF
ON
STOP
RUN
RUN
STOP
Contact image 
memory 
(X, Y, M, S)
Input relay (X)
Cleared.
Does not 
change.
Cleared.
Does not change while M8033 is 
ON.
Output relay (Y)
Cleared.
Does not 
change.
Cleared.
Does not change while M8033 is 
ON.
General type auxiliary relay (M)
Cleared.
*1
Does not 
change.
Cleared.
Does not change while M8033 is 
ON.
Latched (EEPROM backed) type
auxiliary relay (M)
Does not change.
Special type auxiliary relay (M)
Cleared.
Set to initial 
values.
*2
Does not change.
*2
General type state relay (S)
Cleared.
*1
Does not change.
Latched (EEPROM backed) type
state relay (S)
Does not change.
Annunciator (S)
Does not change.
Timer contact
Time counting coil
Reset coil (T)
For 100 ms
Cleared.
Does not 
change.
Cleared.
Does not change while M8033 is 
ON.
For 10 ms
Cleared.
Does not 
change.
Cleared.
Does not change while M8033 is 
ON.
For 1 ms
Cleared.
Does not 
change.
Cleared.
Does not change while M8033 is 
ON.
Retentive type for 100 ms
Does not change.
Retentive type for 1 ms
Does not change.
Counter contact
Counting coil
Reset coil (C)
General type
Cleared.
Does not 
change.
Cleared.
Does not change while M8033 is 
ON.
Latched (EEPROM backed) type
Does not change.
High-speed type
Does not change.