Programming Manual - Basic & Applied Instruction Edition
16 External FX Device – FNC 80 to FNC 89
16.9 FNC 88 – PID / PID Control Loop
*1.
+20 to 
+24 are occupied when any bit 1, 2 or 5 is set to "1" in 
+1 for operation setting
(ACT).
+20
*1
Input variation (incremental) 
alarm set value
0 to 32767
It is valid when bit 1 is set to "1" in 
+1 for 
the operation setting (ACT).
+21
*1
Input variation (decremental) 
alarm set value
0 to 32767
It is valid when bit 1 is set to "1" in 
+1 for 
the operation setting (ACT).
+22
*1
Output variation (incremental) 
alarm set value
0 to 32767
It is valid when bit 2 is set to "1" and bit 5 is set to 
"0" in 
+1 for the operation setting (ACT).
Output upper limit set value
−32768 to 32767
It is valid when bit 2 is set to "0" and bit 5 is set to 
"1" in 
+1 for the operation setting (ACT).
+23
*1
Output variation (decremental) 
alarm set value
0 to 32767
It is valid when bit 2 is set to "1" and bit 5 is set to 
"0" in 
+1 for the operation setting (ACT).
Output lower limit set value
−32768 to 32767
It is valid when bit 2 is set to "0" and bit 5 is set to 
"1" in 
+1 for the operation setting (ACT).
+24
*1
Alarm output
bit0
0: Input variation (incremental) is not 
exceeded.
1: Input variation (incremental) is 
exceeded.
It is valid when bit 1 is set to "1" or bit 2 is set to 
"1" in 
+1 for the operation setting (ACT).
bit1
0: Input variation (decremental) is not 
exceeded.
1: Input variation (decremental) is 
exceeded.
bit2
0: Output variation (incremental) is not 
exceeded.
1: Output variation (incremental) is 
exceeded.
bit3
0: Output variation (decremental) is 
not exceeded.
1: Output variation (decremental) is 
exceeded.
The setting below is required when the limit cycle method is used (when bit 6 is set to "ON" in the operation setting (ACT)).
+25
PV value threshold 
(hysteresis) width (SHPV)
Set it according to the fluctuation of the 
measured value (PV).
They are occupied when bit 6 is set to "ON (limit 
cycle method)" in the operation setting (ACT).
+26
Output value upper limit (ULV)
Set the maximum value (ULV) of the 
output value (MV).
+27
Output value lower limit (LLV)
Set the minimum value (LLV) of the 
output value (MV).
+28
Wait setting from end of tuning 
cycle to start of PID control 
(Kw)
−50 to 32717%