22 External Device – FNC170 to FNC179
22.4 FNC177 – WR3A / Write to Dedicated Analog Block
22.4
FNC177 – WR3A / Write to Dedicated Analog Block
Outline
This instruction writes a digital value to the analog block FX
0N
-3A
*1
 or FX
2N
-2DA.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 16-bit operation (WR3A)
m1 
: Special block number
FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 (D, DS, DSS)
 
PLCs : K0 to K7
FX
3UC
-32MT-LT(-2) : K1 to K7 (K0 indicates the built-in CC-Link/LT master.)
m2 
:  Analog output channel number
FX
0N-
3A
*1
: K1 (ch 1)
FX
2N
-2DA : K21 (ch 1) or K22 (ch 2)
: Data to be written
Specify a value output to the analog block.
FX
0N
-3A
*1
: 0 to 255 (8 bits)
FX
2N
-2DA : 0 to 4095 (12 bits)
*1.
The FX
0N
-3A is available only for the FX
3U
 and FX
3UC
 PLCs.
Operand Type
Description
Data Type
m1 
Special block number
- FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 (D, DS, DSS) PLCs: K0 to K7
- FX
3UC
-32MT-LT(-2)  : K1 to K7
16-bit binary
m2 
Analog output channel number
16-bit binary
Data to be written or word device storing data to be written
16-bit binary
Oper-
and 
Type
Bit Devices
Word Devices
Others
System User
Digit Specification
System User
Special 
Unit
Index
Con-
stant
Real 
Number
Charac-
ter String
Pointer
X Y M T C S D .b KnX KnY KnM KnS T C D R U \G
V Z Modify K H
E
" "
P
m1 
m2 
P
FNC 177
WR3A
Mnemonic
Operation Condition
16-bit Instruction
 7 steps
WR3A
WR3AP
Mnemonic
Operation Condition
Continuous
Operation
Pulse (Single)
Operation
32-bit Instruction
  S
  S
FNC177
WR3A
m1
m2
Command
input
   
S