Mitsubishi Electronics FX3G User Manual

Page of 964
692
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series
Programming Manual - Basic & Applied Instruction Edition
30 External Device Communication – FNC270 to FNC276
30.4 FNC273 – IVWR / Inverter Parameter Write
2. Related devices
→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.
*1.
Cleared when PLC power supply is turned from OFF to ON.
*2.
Cleared when the PLC mode switches from STOP to RUN.
*3.
Initial value: -1
Cautions
→ For other cautions, refer to the Data Communication Edition manual.
• It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"FLCRT (FNC300) to FLSTRD 
(FNC305)" instruction and an "IVCK (FNC270) to IVMC (FNC275)" instruction for the same port.
• Two or more inverter communication instructions (FNC270 to FNC275) can be driven for the same port at the same 
time.
• Cautions on using the password function in the D700 Series.
1) When a communication error occurs
When a communication error occurs in an inverter communication instruction, the FX PLC automatically retries
communication up to 3 times
*4
.
Accordingly, note that the number of times of password reset error displayed in accordance with the setting of
Pr297 may not agree with the actual number of times of password input error as described below when a
password reset error occurs in the D700 Series in which "display of the number of times of password reset error"
*5
is made valid using Pr297.
Do not execute automatic retry (re-driving of an inverter instruction) using a sequence program when writing data
to Pr297.
Cases in which a password reset error occurs in an inverter communication instruction, and the actual number of
times of reset error in such cases.
-
When a wrong password is written to Pr297 due to a password input error
When the writing instruction is executed once, a password reset error occurs 3 times.
-
When the password cannot be written correctly to Pr297 due to noise, etc.
A password reset error occurs up to 3 times.
2) When registering the password
When registering the password in the D700 Series inverter using an inverter communication instruction, write the
password to Pr297, read Pr297, and then confirm that registration of the password is completed normally
*6
.
If writing of the password to Pr297 is not completed normally due to noise, etc., the FX PLC automatically retries
writing, and the registered password may be reset by the retry.
*4.
The FX PLC executes the first communication, and then retries communication twice (3 time in total).
*5.
When "display of the number of times of password reset error" is made valid in the D700 Series using Pr297
and when a password reset error occurs 5 times, the "reading/writing restriction" cannot be reset even if the
right password is input.
For recovery from this status, it is necessary to all-clear all parameters in the D700 Series.
*6.
When the value given as a result of reading Pr297 is "0" to "4", registration of the password is completed
normally.
PLC applicable version
The table below shows PLC versions applicable to each inverter.
Number
Description
Number
Description
ch1
ch2
ch1
ch2
M8029
Instruction execution complete
D8063
D8438
Error code of serial communication error
*1
M8063
M8438 Serial communication error
*1
D8150
D8155
Response wait time in inverter communication
*1
M8151
M8156 Inverter communicating
D8151
D8156
Step number in inverter communication
*3
M8152
M8157 Inverter communication error
*2
D8152
D8157
Error code of inverter communication error
*2
M8153
M8158 Inverter communication error latch
*2
D8153
D8158
Latch of inverter communication error occurrence
step
*2*3
M8154
M8159 IVBWR instruction error
*2
D8154
D8159
IVBWR instruction error parameter number
*2*3
PLC
FREQROL-V500/F500/A500/E500/S500
FREQROL-F700/A700
FREQROL-E700/D700
FX
3S
Ver. 1.00 or later
FX
3G
Ver. 1.10 or later
FX
3GC
Ver. 1.40 or later
FX
3U
Ver. 2.20 or later
Ver. 2.32 or later
FX
3UC
Ver. 1.00 or later
Ver. 2.20 or later
Ver. 2.32 or later